Specifications
CC-Link
AJ65SBT-64AD Analog to Digital Conversion Module
●
Four analog input (voltage input/current input) channels are provided.
●
Greater accuracy and higher resolution than the AJ65BT-64AD has been realized.
●
Separate analog input ranges can be set for each channel.
●
By incorporating a movement averaging process, the averaging process can be
carried out without changing the conversion speed.
●
The installation area is 60% smaller and the volume is 38% smaller than the
AJ65BT-64AD.
AJ65SBT-62DA Digital to Analog Conversion Module
●
Two analog output (voltage output/current output) channels are provided.
●
Greater accuracy and higher resolution than the AJ65BT-64DAV/DAI has been
realized.
●
Separate analog output ranges can be set for each channel.
●
The installation area is 60% smaller and the volume is 38% smaller than the
AJ65BT-64DAV/DAI.
■ Specifications: Analog to digital conversion
Model
AJ65SBT-64AD
Voltage input Current input
Digital output −10 to 10VDC (input resistance 1MΩ) 0 to 20mADC (input resistance 250Ω)
Analog input −4096 to 4095
Analog input Digital output Analog input Digital output
−10 to 10V 0 to 5V 1 to 5V — 0 to 20mA 4 to 20mA —
Input/Output characteristics
−10V ——−4000 ———
0V 0V 1V 0 0mA 4mA 0
5V 2.5V 3V 2000 10mA 12mA 2000
10V 5V 5V 4000 20mA 20mA 4000
Maximum resolution 2.5mV 1.25mV 1mV — 5µA 4µA —
Accuracy Within ±0.2% (25±5°C), Within ±0.4% (0 to 55°C)
Conversion speed 1ms/channel
Number of analog input points 4 channels/module
Offset/gain adjustment Provided (user setting or factory setting)
Number of occupied input/output points 1 station: RX/RY 32 points each
(station type) RWr/RWw 4 points each (remote device station)
■ Specifications: Digital to analog conversion
Model
AJ65SBT-62DA
Voltage input Current Input
Digital Output −4096 to 4095 0 to 4095
Analog input
−10 to 10VDC 0 to 20mADC
(External load resistance: 2kΩ to 1MΩ) (External load resistance: 0 to 600MΩ)
Digital output Analog input Digital output Analog input
— −10 to 10V 0 to 5V 1 to 5V — 0 to 20mA 4 to 20mA
Input/Output characteristics
−4000 −10V —————
0 0V 0V 1V 0 0mA 4mA
2000 5V 2.5V 3V 2000 10mA 12mA
4000 10V 5V 5V 4000 20mA 20mA
Maximum resolution — 2.5mV 0.625mV 0.5mV — 5µA 4µA
Accuracy Within ±0.2% (25±5°C), Within ±0.4% (0 to 55°C)
Conversion speed 1ms/channel
Output short-circuit protection Provided
Number of analog input points 2 channels/module
Offset/gain adjustment Provided (user setting or factory setting)
Number of occupied input/output points 1 station: RX/RY 32 points each
(station type) RWr/RWw 4 points each (remote device station)