Specifications
CC-Link
Communication
Minimum distance between stations Overall distance
speed
Standard CC-Link ver.1.00 Standard CC-Link ver.1.10 Standard CC-Link ver.1.00 Standard CC-Link ver.1.10
156k bps 1200m (3,937 ft) 1200m (3,937 ft)
625k bps 30cm (11.8 inch) or longer 600m (1,969 ft) 900m (2,953 ft)
2.5M bps 200m (656 ft) 400m (1,312 ft)
5M bps
60cm (23.62 inch) or longer 20cm (7.9 inch) 150m (492 ft)
160m (525 ft)
30cm (11.8 inch) to 59cm (23.23 inch)
110m (361 ft)
1m (3.28 ft) or longer 100m (328 ft)
10M bps
60cm (23.62 inch) to 99cm (38.98 inch)
80m (262 ft) 100m (328 ft)
30cm (11.8 inch) to 59cm (23.23 inch)
50m (164 ft)
■ Specifications: Network
Item Specifications
Transmission speed 156k/625k/2.5M/5M/10M bps
Maximum distance 1200m (limited to 156kbps)
64 stations, however the following conditions apply:
{(1×a)+(2×b)+(3×c)+(4×d)}≤64
a: number of 1 station modules
b: number of 2 station modules
Maximum number of connected stations
c: number of 3 station modules
d: number of 4 station modules
{(16×A)+(54×B)+(88×C)}≤2304
A: number of remote I/O station modules ≤64
B: number of remote device stations ≤42
C: number of local, stand-by master and intelligent device stations ≤26
Remote I/O (RX, RY): 2048 points
Maximum network data per network system Remote register (RWw): 256 points (master to local/remote)
Remote register (RWr): 256 points (local/remote to master)
Remote I/O (RX, RY): 32 points (30 points for local)
Maximum network data per local/remote station Remote register (RWw): 4 points (master to local/remote)
Remote register (RWr): 4 points (local/remote to master)
Communication method Polling
Synchronization method Frame synchronization
Modulation NRZI
Transmission path Bus (RS485)
Frame format HDLC
Frame check sequence CRC
Applicable cable Shielded twisted pair cable
Automatic communication return function
RAS function Slave station cut-off
Error detection by special link relays/registers
Number of parameter registration 10,000 times
Occupied I/O points 32 points
5VDC consumption A1SJ61BT11: 0.4A
■ Specifications: Communication speed & distance
36
Note: All the CC-Link modules are now compatible with CC-Link ver. 1.10 step by step. Modules compatible with CC-Link ver. 1.10 have on their side a “CC-Link” seal.