Specifications

MELSECNET/IIB
MELSECNET II
MELSECNET/B
Choice of cable
The MELSECNET system offers a choice of four different
varieties of cable. These range from the low cost twisted
pair cable bus to dual coaxial cable to the highly reliable
GI dual fiber optic cable network.
MELSECNET/B refers to the twisted pair cable bus system,
while MELSECNET II to both coaxial and fiber optic
systems. The software of both systems, however, provides
the same range of functions.
Loopback function (MELSECNET II only)
The MELSECNET II data link system uses two parallel cable
loops for connecting PLC stations, a forward (main) loop
and a reverse (sub) loop. In the event of a break in the main
loop, communications will be automatically switched to the
sub loop maintaining the data link system. If there is a
break in both loops, communications will continue among
the remaining connected stations as shown.
Link up to 32 or 65 stations
In MELSECNET II system, one master and 64 slave stations
can be connected per network. For MELSECNET/B, one
master and 31 slave stations can be connected per network.
MELSECNET II, MELSECNET/B
A high speed, high reliablity
data link system
High speed transmission
A coaxial or fiber optic cable system is capable of
transmitting data at 1.25M bps speed while the twisted pair
cable system can transmit at 1M bps maximum.
M
L7
L1
L6
L5
L4
L3
L2
Sub Loop
Main Loop
33