Specifications
A616DAV/ I
A616AD
Temperature detection in each room
Heater adjustment
in each room
■
High speed, high density analog modules for advanced applications
■
A616 analog module specifications
■
System configuration example
The A616 high density modules provide increased power
and more flexible analog I/O capability. Both the analog
input and output modules have sixteen channels per
module; seven of which can be combined with multiplexer
units. Utilizing these yields a maximum total of 121
channels per base module. The multiplexer units are
available in three different types. One which provides
isolated channels; another which gives non-isolated
channels, and one which is for use with the thermocouple
input module.
Part number A616AD A616DAV/A616DAI A60MX/A60MXR/A60MXT
Applicable QnA/A Series PLC QnA/A Series
Number of I/O points
required
Number of output channels 16 channels 16 channels 16 channels
Overall accuracy ±0.3% ±0.5% ±0.2%
Maximum conversion time 1ms/channel 0.5ms/channel
External power supply Not required
Digital input/output
Maximum resolution 1/4000
Analog output/input
V input: -10 to 0 to +10 VDC.
Input resistance
1M ohms
I input; 4 to +20 mA,
Input resistance 250 ohms
V output; -5/10 to 0 to +5/10 VDC
I output; 0 to 20mA
Output; -48 to 4047 or -2048 to
+2047
Input; V -4096 to +4095,
I 0 to 4095
Absolute maximum analog
output/input
V input; ±15 VDC
I input; ±30mA
V input; ±12VDC
I input; ±28mA
Voltage: 1.3/0.65 mV
Current: 2.64
µA
Photo coupler insulation between input terminals
and internal circuitry
No insulation between channels
Insulation method
As per base module connected to
As per base module connected to
As per base module connected to
As per base module connected to
As per base module connected to
-15, 0, +15 VDC
(from A68P)
A60MX - no insulation between
channels
A60MXR - insulation between
channels
As per base module connected to
32 points 32 points 16 points
■
A616 Series analog modules
Analog Modules
19