Specifications
Analog voltage
Start/stop signal
Drive unit
Motor
Machine
Analog output modules are available for all MELSEC QnA/A
Series PLCs. Like the analog input modules each has a built-
in microprocessor, which converts binary digital signals to
either current or voltage analog signals. Offset and gain
values for the output signal can also be set and retained in
the microprocessor.
■
System configuration example
■
Analog output modules
■
Intelligent D/A conversion using built-in microprocessors
Part number A62DA
Applicable QnA/A Series PLC QnA/A Series
Number of output channels 2 channels
Analog output
Voltage: -10 to 0 to +10, external load 500k - 1M ohms
Current: +4 to +20 mA, external load, 0 - 600 ohms
Digital input ±2000 for voltage, ±1000 for voltage
Maximum resolution Voltage: 5 mV (1/2000), Current: 20 µA (1/1000)
Overall accuracy ±1%
Maximum conversion time 16ms
Absolute maximum analog output Voltage: ±12 VDC, Current: 28 mA
Insulation method
Photocoupler insulation between input terminals and internal circuity
No insulation between channels
External power supply 24VDC
I/O points required 32 points
■
Analog output modules specifications
Analog Modules
18