Specifications

Analog Modules
A68AD
Analog voltage/current
Welder
Analog input module specifications
Analog input modules are available for all MELSEC QnA/A
Series PLCs. Each is capable of accepting either current or
voltage variable input signals. These signals are then
converted in to a binary value by a built-in microprocessor,
and can then be used for processing within the sequence
program. Input signals can be instantaneously read, or they
can be sampled for user programmable time/count
averaging processing. Setting offset and gain values for the
converted values is also possible.
Intelligent A/D conversion using built-in microprocessors
System configuration example
Part number A68AD (-S2)
Applicable QnA/A Series PLC QnA/A Series
Number of output channels 8 channels
Analog output
Voltage: -10 to 0 to +10, input resistance 30k ohms
Current: +4 to +20 mA, input resistance 250 ohms
Digital input -2048 to +2047
Maximum resolution Voltage: 5 mV (1/2000), Current: 20 µA (1/1000)
Overall accuracy ±1%
Maximum conversion time 2.5 ms
Absolute maximum analog output Voltage: ±15 VDC Current: ±30 mA
Insulation method
Photocoupler insulation between input terminals and internal circuity
No insulation between channels
I/O points required 32 points
Note: The A68AD-S2 type and log input module can be specially used to set a valid/invalid flag for the A/D transfer of each channel.
A68AD/A68AD-S2
Analog input modules
17