6-3 System-Changeover of Y series 
Click on [Function2]-[Auto-changeover] in the menu to open the auto-changeover screen and make necessary 
settings to switch the operation mode between cooling and heating automatically of the indoor units connected 
to the same outdoor unit. Set the change over mode and the target units. 
Please use this function when performing heating operation in the morning and cooling operation in the 
afternoon on air conditioners that either of cooling or heating operation is possible (Y series). The operation 
mode changes automatically without the need of operating all remote controllers. 
Note: If PAC-YG50ECA Expansion Controllers are connected, Expansion Controller system selection buttons will appear. Select 
the desired Expansion Controller (EC1, EC2, or EC3), and make the settings for each system. Make the settings with the 
Expansion Controllers properly connected. 
Note: The operation mode (cooling or heating) is set by the majority decision in consideration of performance value of each unit, 
or on the basis of the operation mode of the representative group. Therefore, some rooms may be hotter or colder than 
others. 
Note: If the user logs in as a building manager, the operations may be prohibited. 
Note: Set the indoor unit operation mode to [Auto] on the Auto-Changeover models (R2 series). (It is not necessary to change the 
mode on this screen.) 
Note: When connecting AG-150A controllers by connecting an Expansion Controller to the system, auto-changeover settings 
should be made only on one of the AG-150A controllers. 
(1) Select the change mode of the target outdoor unit. When selecting the representative group mode, select 
one representative group among the member groups. 
Table 6-1 Change Mode List 
Change mode  Content 
None  Select this when the function is not used. 
Averaging 
The operation mode (cooling or heating) is set and changed by the majority 
decision in consideration of the set temperature, the room temperature 
difference of all groups connected to the target outdoor unit, and capacity 
value of each indoor unit. 
Representative Group 
Changes the set temperature of the representative group, and the operation 
mode of the member group in accordance with the temperature difference. 
(2) Click [Save Settings] to send setting data to the AG-150A. 
Save settings 
Send setting data to AG-150A.
Target outdoor units
The M-NET address of the 
outdoor unit is displayed here.
Member group 
The group name that is 
connected to the outdoor unit 
is displayed here. 
When the representative 
group mode is selected, select 
the representative group 
among these member groups.
Changeover mode
The changeover mode is 
displayed here.
Refresh 
Read setting data from AG-150A. 
Expansion Controller 
system selection buttons 
Click to select the system to be set.