Installation manual

- 14 -
Before performing a test run, verify that the group setting has been performed and the startup sequence for the interlocked
operation setting has been completed.
It may take approximately 10 minutes from power on until the local remote controller becomes operable. By pressing the operation/
Stop button on the touch panel on AG-150A the remote controller will become operable right away.
Test run procedure
1 Turn the AG-150A and all air conditioning units on.
2 Select the group to be tested on the Monitor/Operation screen and run the test.
3 Check for proper operation of each air conditioning unit during test run (e.g., check to see if cold (or warm) air comes out of the
supply air outlet on each indoor unit)
4 After confirming that all units are operating properly, stop the units either from AG-150A or from the remote controllers.
* Please refer to the Install Manual that came with the indoor unit for further details on the test run method.
1. To control a K control model
* Set AG-150A address to “000” when a K transmission converter is
connected. Always set to the main system controller when the
address is “000”.
* Set the address of the K-control indoor units to a larger number
than those of the M-transmission models of indoor units.
* When using a group setting for the K control model, set only the
indoor unit that belongs to that group.
* Set the minimum indoor unit address in the group for the K control
model group number.
1. External signal input function
* External signal input requires the external I/O adapter (PAC-YG10HA) sold separately.
(1) External input
Emergency stop/normal, run/stop and prohibit/enable operation of local remote controllers can be controlled for all grouped air
conditioners by using a voltage (12VDC or 24VDC) contact signal from an external source. (Select with an initial settings screen.)
(2) Level signals and pulse signals (12VDC or 24VDC)
9Test Run
10 System Configuration Example
11 External input/output usage
No. External signal input function Remarks
1
Do not use the external input signal
(factory setting)
-
2
Perform emergency stop/normal with
level signal
The local remote controller ON/OFF operation, the controller ON/OFF operation,
and prohibit/enable change operation will be prohibited during emergency stop.
Timer operation will also be prohibited.
3 Perform ON/OFF with level signal
The local remote controller ON/OFF operation, the controller ON/OFF operation,
and prohibit/enable change operation will be prohibited. Timer operation will also
be prohibited.
4
Perform ON/OFF, prohibit/enable with
pulse signals.
Set the pulse width while the contact is ON to 0.5 to 1 second.
(A) Level signal (B) Pulse signal
* The prohibit/enable input is the same.
20 indoor units
Indoor unit address 01~20
Group 1 to Group 20
20 indoor units (for control)
Indoor unit address 21~40
Group 21 to Group 40
M-NET
PAC-SC51KUA
Power supply unit
24VDC
(Main system controller)
AG-150A
PAC-SC25KAA
K transmission converter
Contact ON
Contact OFF
Stop Run Stop
Normal Normal
Emergency
stop
Contact ON
Contact OFF
Example for ON/OFF
Signal 1(run)
Signal 2(stop)
0.5 to 1 sec
0.5 to 1 sec
OFFONOFF
Contact ON
Contact OFF
Contact ON
Contact OFF