Specifications

98AEtypMMSspec_RevB.doc
8
Copyright © 2007, Mitsubishi Electric Power Products Inc.
SP-0011 Rev. B 9/5/09
7. Grounding Continuity
8. Insulation strength test
9. Control Circuit Operation
10. Measurement of steady state characteristics (Voltage/ current/ efficiencies)
11. Transient characteristics (0-100% step load, without batteries/ voltage
fluctuation)
12. Overload Testing
13. Transfer switch operation
2. PRODUCT
2.1. THE UPS SHALL HAVE THE FOLLOWING ELECTRICAL CHARACTERISTICS
2.1.1. UPS MMS Capacity
The 9800A Series UPS Module is available in the following sizes:
kVA kW
100 80
150 120
225 180
300 270
375 337.5
500 450
750 675
Up to Eight (8) UPS Modules of equal kVA size may be paralleled together to
provide the required UPS MMS capacity or redundancy.
UPS Module output capacities are in accordance with the following power factors:
A. 100 kVA ~ 225 kVA 0.8 pf lagging
B. 300 kVA ~ 750 kVA 0.9 pf lagging
2.1.2. UPS Module AC Input Specification
A. Configuration: 3-phase, 3-wire
B. Nominal Input Voltage: 480V
C. Input Voltage Range: +15%, -15%
D. Input Frequency and Range: 60 Hz 5%
E. Input Power Factor: 0.98 (Typical) at 100% Load, 0.90 (Typical) at 50% Load
F. Reflected Input Current: 6% (Typical) at 100% Load, 9% (Typical) at 50% Load
2.1.3. UPS Module Bypass Input Specification
A. Configuration: 3-phase, 4-wire
B. Nominal Input Voltage: 480V, 600V
C. Input Synchronization Voltage Range: 10% of Nominal
D. Input Frequency Tracking Range: 60 Hz 5% Maximum [Bypass Synchronous
range shall be selectable from 1% to 5% in 1% increments]
2.1.4. UPS Module Output Specification