Specifications

98AEtypMMSspec_RevB.doc
6
Copyright © 2007, Mitsubishi Electric Power Products Inc.
SP-0011 Rev. B 9/5/09
Monitoring System.
J. Monitoring System Operation - The Monitoring System will monitor all UPS MMS
components and display UPS MMS operational status and information on the Human
Machine Interface (HMI). UPS MMS operation sequences shall also be possible from the
Monitoring System HMI, and system summary alarm and user selectable system alarm
contacts available.
1.5. SUBMITTALS
1.5.1. Proposal Submittals
Submittals with the proposal shall include;
A. System configuration with single line drawings.
B. Functional relationship of equipment including weights, dimensions, and heat
dissipation.
C. Descriptions of equipment to be furnished, including deviations from these
specifications.
D. Size and weight of shipping units to be handled by installing contractors.
E. Detailed layout of customer power and control connections.
F. Detailed installation drawings including all terminal locations
1.5.2. Delivery Submittals
Submittals upon UPS delivery shall include;
A. Shop Drawings - Submit system configurations with single line diagrams,
detailed layout of power and control connections, dimensional data and
detailed installation drawings including all terminal locations.
B. Product Data - Provide product data for UPS and battery including catalog
sheets and technical data sheets to indicate electrical performance, UPS type,
battery type, detailed equipment outlines, weight, dimensions, control and
external wiring requirements, heat rejection and air flow requirements.
C. Owners and technical manual (1).
D. Test Report - Submit a copy of factory and field test reports.
1.6. ENVIRONMENTAL CONDITIONS
A. The UPS shall be capable of withstanding any combination of the following external
environment conditions without mechanical damage, electrical failure or degradation of
operating characteristics.
1. Operating ambient temperature: 0 degrees C to +40 degrees C (32 degrees F to
104 degrees F) no derating required.
2. Recommended operating temperature range: +20 degrees C to +30 degrees C
(68 degrees F to 86 degrees F).
3. Non-operating and storage ambient temperature: -20 degrees C to +70 degrees
C (-4 degrees. F to 158 degrees F).
4. Operating relative humidity: 5% to 95 %, non-condensing.
5. Recommended operating relative humidity: 30 % to 90%.
6. Operating altitude: Sea level to 2700 meter (9000ft).