NEMA standard for floor mounting. The UPS shall be equipped with standard
forklift provisions to allow ease of installation using conventional lifting/moving
equipment. The UPS module cabinet shall have hinged and lockable doors on
the front only. Operating controls shall be located outside the locked doors.
Input, output, and battery cables shall be installed through the top or bottom of
the cabinet.
2.4.2. Serviceability
The UPS shall have front access for all servicing adjustment and connections only
for maintenance or service. Side access or rear access shall not be accepted. The
UPS shall be designed such that its rear can be pressed against a back wall and
its sides can be pressed against side walls.
2.4.3. Ventilation
Forced air cooling shall be provided to allow all components to operate within their
rated temperature window. Thermal relays, using a latched contact which is
capable of being reset, shall be used as overload protection to all cooling fans.
Each fan shall employ a separate thermal relay. All air inlets use washable air
filters that shall be removable from the front of the UPS without exposure to any
electrical hazard. Air filters shall be door mounted to prevent floor dust from being
sucked into the unit. Bottom mount air filters shall not be accepted.
2.4.4. Busbar
All busbar used for conductivity within the UPS shall be designed with COPPER
ONLY. Aluminum busbar are not acceptable.
2.4.5. (Option) Eyebolts
Eyebolts shall be installed for lifting UPS. Four (4) heavy duty eyebolts will be
installed on each corner on top of UPS. Eyebolts are detachable (unscrew
manually) once UPS is set in installation area.
3. EXECUTION
3.1. SITE PREPARATION
The owner shall prepare the site for installation of the equipment.
3.2. INSTALLATION
A. The UPS shall be set in place, wired and connected in accordance with the approved
installation drawings and owners/technical manual delivered with equipment.
B. The equipment shall be installed in accordance with local codes and manufacturer’s
recommendation.
3.3. FIELD QUALITY CONTROL