b. UPS Module component and CLC CB color status indication.
c. System input and output measurement data.
d. Screen selection icons
2. Individual UPS Module information:
a. UPS Module mimic display and power flow.
b. UPS Module component color status indication.
c. UPS Module input and output measurement data.
d. UPS Module Battery Data
e. Screen selection icons
3. System Event and Alarm information (History log).
a. UPS Module Alarm and event Groups.
b. Alarm and event history
4. System Alarm Output Selection - PLC Output. PLC Outputs can be
configured to give dry contact signals for alarm purposes:
a. Summary alarm
b. UPS Module Alarm
c. System Sync to Bypass
d. System Overload
5. Operator sequence function screen (Password protected). (UPS MMS
Inverter Operation UPS MMS Bypass Operation)
6. All individual UPS Module LCD display information is available for display
on the HMI, with the GOT accessing the data via the Ethernet. Refer to the
previous section UPS Module Operation/Display Panel LCD for detailed
information on available UPS Module data.
7. The CLC Monitoring System GOT can also be remotely monitored on a
web browser. No additional software will be required for the remote PC,
with Internet Explorer only required to web monitor. Refer to Monitoring
System Operation Manual for further details.
8. System Emergency Power Off (System EPO):
The System EPO button shall be located on the CLC next to the Monitoring
System HMI. The System EPO contacts shall be hard wired to each
system UPS Module external signal terminal block (Input terminal
Remote EPO). When the System Emergency Power Off (EPO) button is
activated, the EPO function will shutdown all UPS Modules and the load
will be dropped.
2.4. MECHANICAL DESIGN
2.4.1. Cabinet Structure (Enclosure)
A. The enclosure shall be primed and painted with the Munsell 5Y7/1 (beige)
color. The enclosure shall be free standing floor mount design. The enclosure
panels and doors shall consist of minimum 14 gage steel for maximum
strength and durability.
B. The UPS shall be installed in cabinets of heavy-duty structure meeting with