2.3.2. SMB and 52L circuit breaker and associated power circuits
The CLC contains power circuit. The system bypass source is a common feed to
the UPS Module bypass inputs and also the CLC System Maintenance Bypass
input. An electro-mechanical interlock system will prevent closure of the SMB
circuit breaker and subsequent opening of 52L circuit breaker unless UPS MMS
Bypass Operation is active. Refer to previous section System Maintenance
Bypass Operation.
System Maintenance Bypass Operation shall allow total system repair and testing
for parallel operation as well as individual UPS Module repair and testing without
affecting load operation as standard a System Maintenance Bypass circuit breaker
(SMB) and power circuit, and a System Output circuit breaker (52L) and output
A. SMB/52L Interlock System:
An electro-mechanical interlock system will be included as standard. The
Interlocking System shall be used for controlling initiation of System
Maintenance Bypass Operation and offer the following safety functions:
B. Interlock Principle:
To prevent the closure of System Maintenance Bypass Circuit Breaker SMB
while the system is operating on UPS Inverter mode. (Possible connection of
out of phase sources).
To force sequence of operation to isolate UPS MMS (UPS Modules) from
System Maintenance Bypass power supply for maintenance and testing
requirements.
2.3.3. CLC Monitoring Section
A. The Monitoring System main Graphical Operator Terminal (GOT) shall be the
Monitoring System Human Machine Interface (HMI) and shall be located on
the CLC door exterior. All information will be displayed and operator control
sequences initiated from the HMI. The GOT will be directly interfaced to each
UPS Module LCD via Ethernet (10Base-T and Hub) and will have access to all
system UPS Module data via this network. The GOT will be serial connected to
the Monitoring System PLC.
B. The PLC performs logic functions required for the HMI screen display
requirements and also for performing operator sequences. The PLC inputs will
also accept the CLC circuit breaker status contacts for HMI display information.
The PLC outputs shall be utilized for system summary alarm and user
selectable system output alarms (selectable from the HMI). GOT software (for
HMI screen display information and touch screen functions), and the PLC
ladder sequence control program will create the Monitoring System user
environment and operational architecture. UPS MMS configuration, UPS
Module and UPS quantity will be selectable for HMI display information.
C. The HMI (GOT) displays different screen information according to user request.
Typical information screens are:
1. Main Overview:
a. Total UPS MMS mimic display and power flow.