Specifications
98AEtypMMSspec_RevB.doc
20
Copyright © 2007, Mitsubishi Electric Power Products Inc.
SP-0011 Rev. B 9/5/09
Download Alarm and System Event log to PCRS 232 Communication
2.2.11. External signal interface terminal
The UPS Module is equipped with a series of input/output terminals for external
annunciation of alarms and for remote access of certain UPS functions.
A. Terminals OUT 1 to OUT 6 are user programmable, with the default settings:
a. OUT 1: Load on Bypass
b. OUT 2: Load on Inverter
c. OUT 3: Battery Operation
d. OUT 4: Rectifier Operation
e. OUT 5: Battery Low Voltage
f. OUT 6: Overload
B. Terminals IN 1 to IN 5 offer the following remote functions:
a. IN 1: Remote Start
b. IN 2: Remote Stop
c. IN 3: Battery Temperature Abnormal
d. IN 4: Input Power Demand
e. IN 5: Remote Emergency Power Off) (EPO)
2.2.12. (OPTION) DiamondSync
The UPS manufacture shall offer a Sync circuit which shall allows any two or more
different UPS modules to sync into a master Sync source. The circuit allows both UPS
modules to operate in to a common output transfer cabinet and allows the load continue to
operate without any degradation to the load.
2.2.13. (OPTION) Common Battery
The customer is to advise if each UPS module is to have its own dedicated smaller battery
bank or if one large battery bank is required to operate the entire load.
2.3. CLC COMPONENTS
For additional information to below, refer to the Mitsubishi Electric CLC Specification.
2.3.1. CLC Power Section
Bypass Load Sharing Reactors (ACL1, ACL2 up to ACL8 depending on system
UPS Module quantity)
For equal load sharing, a load sharing reactor shall be incorporated in each UPS
Module circuit to ensure bypass line impedance balance and that each bypass line
supports an equal share of the total load current during bypass operation. Each
UPS Module circuit reactor will be located in the CLC. Refer to previous section
UPS MMS Bypass operation.










