Specifications

98AEtypMMSspec_RevB.doc
19
Copyright © 2007, Mitsubishi Electric Power Products Inc.
SP-0011 Rev. B 9/5/09
c. Battery Operation
d. Output Overload
e. Rectifier Operation
f. Inverter Running Synchronously
g. Static Bypass Input Out of Range
h. Minor Fault Data
i. Major Fault Data
B. LED indication
The Operation/Display Panel contains the following LED indication:
a. Load on Inverter (Green)
b. Battery operation (Yellow)
c. Load on Bypass (Green)
d. Overload (Red)
e. LCD Fault (Red)
f. UPS Fault (Red)
C. Emergency Power Off (EPO) button
When the UPS Module Emergency Power Off (EPO) button is activated, the
EPO function shuts down the UPS module. The configuration of the UPS
MMS will depict the subsequent system operation. Refer to previous section
Individual UPS Module EPO. The EPO function can be performed both locally
at the UPS Module and remotely from the CLC System EPO button. When
remote EPO is performed, all system UPS Modules will be shutdown and the
critical load dropped.
2.2.8. UPS status and function interface
In addition to the communication capabilities of the UPS Module LCD, the
following communication methods are available: RS-232C/RS-422
Communication Port: The UPS Module will have as standard a RS-232C/RS-422
port allowing the user to interface to the UPS module offering the following
functions:
2.2.9. Additional UPS Module Monitoring functions
1. Via Personal Computer (PC) - Mitsubishi Electric Diamond Link Software
2. Via Netcom (SNMP/Web Card)
2.2.10. Service functions via PC
Waveform capture trace information: Upon UPS failure, a trigger will initiate
capture of UPS Module Waveform, logic and control signals. The capture duration
will be for 10 cycles, 5 cycles pre trigger and 5 cycles post trigger. The sampling
frequency shall be 7.2kHz, therefore a total of 120 samples per cycle will be taken.
The captured data can be downloaded to a PC and displayed on Mitsubishi
Electric Software. The Software allows selection of UPS Module Waveform, logic
and control signals for display and zoom functions. Waveform capture information
assists service personnel for troubleshooting and undertaking UPS Module failure
root cause analysis.