Specifications

98AEtypMMSspec_RevB.doc
18
Copyright © 2007, Mitsubishi Electric Power Products Inc.
SP-0011 Rev. B 9/5/09
measured values, while also offering operator sequence instructions
(start/stop function etc. - Password protection possible). The LCD panel
allows the user to verify the status and operation of the UPS Module
components by the mimic display. The following information is available
on the MAIN MENU Sheet:
Display information:
a. Bypass Voltage and Frequency
b. Input Voltage and Frequency
c. Battery Voltage (and charge/discharge current)
d. Battery capacity remaining during power failure conditions
e. Output Voltage, Frequency and Current
f. Rectifier operation
g. Battery operation
h. Load on inverter
i. Inverter synchronized with bypass
j. Load on bypass
k. Equalize charge on
l. Alarm/Fault messages
Available operator sequence instructions:
a. Inverter start/stop
b. UPS start up/shutdown
c. Transfer of critical load to bypass source
d. Equalize charge to system battery
(2) MEASUREMENT MENU Sheet:
The MEASUREMENT MENU sheet indicates details of measured values.
The following data will be displayed on the MEASUREMENT MENU
Sheet:
a. Bypass Voltage and Frequency
b. Input Voltage and Frequency
c. Battery Voltage (and charge/discharge current)
d. Battery capacity remaining during power failure conditions
e. Output Power (kW)
f. Output Voltage (all phases including line to line and line to neutral)
g. Output Frequency
h. Output Current in RMS Amps and % (all phases including neutral).
(3) SET UP MENU Sheet:
The SET UP MENU Sheet prompts the user to select specific
performance and UPS setting data. (remote or local start & stop operation,
date & time adjustment, battery equalizing charge availability etc.)
(4) LOG MENU Sheet:
The LOG MENU Sheet indicates event and alarm/fault information and
battery discharge records. A maximum of 50 events can be displayed.
The following alarm/status information shall be available as a minimum:
a. Load on Inverter
b. Battery Low Voltage