Specifications

98AEtypMMSspec_RevB.doc
16
Copyright © 2007, Mitsubishi Electric Power Products Inc.
SP-0011 Rev. B 9/5/09
static switch and shall at the same time as the static switch, be energized and
upon closure maintain the critical load feed from the bypass source. The static
switch shall only be utilized for the time needed to energize the wrap around
contactor therefore increasing reliability. The bypass circuit shall be capable of
supplying the UPS rated load current and also provide fault clearing current
capabilities. The UPS MMS Bypass Operation Control, will upon signaling the
UPS Module Control to initiate transfer to bypass operation, cause the static
switch to energize within 150μs, therefore providing an uninterrupted transfer
to the bypass source (UPS MMS Bypass Operation).
C. In relation to automatic re - transfer from UPS MMS Bypass Operation to UPS
MMS Inverter Operation upon overload clearance. The UPS MMS Bypass
Operation and UPS Module Control shall allow a re-transfer to occur three
times maximum within a one minute period. Re-transfer shall be inhibited upon
the fourth request for protection from a suspect recurring problem at the UPS
load distribution.
D. With each UPS Module incorporating an independent automatic bypass static
switch circuit and associated control; system reduction with the capability to
utilize the removed UPS Module for Single Module System (SMS) application
or other system configurations is possible. This feature results in high system
flexibility, with ease of expansion or reduction of the UPS MMS.
2.2.6. UPS MMS Control
UPS MMS Control, incorporating UPS MMS Parallel and Bypass Operation
Control in each UPS Module utilizes cross current control and inverter operation
logic signals between the UPS Modules to ensure correct UPS MMS operation.
A. UPS MMS Bypass Operation Control:
1. The UPS MMS Bypass Operation Control contained in each independent
UPS Module ensures correct system transfer to and re-transfer from
bypass operation and that UPS MMS Inverter and Bypass Operation will
never occur simultaneously.
2. Referring to the previous section UPS Module Inverter Shutdown,
subsequent to a UPS Module inverter shutdown, the shutdown UPS
Module inverter will automatically isolate from the system, with the UPS
MMS Bypass Control activating a control sequence that upon completion
will signal the UPS Module Control to initiate transfer to bypass operation.
The completion of this control sequence and subsequent initiation of
transfer to bypass operation will be inhibited while the remaining system
UPS Modules can sustain load power from inverter supply.
3. When the UPS MMS Bypass Operation Control in each UPS Module
signals the UPS Module Control to initiate transfer to bypass operation and
therefore initiate system transfer to UPS MMS Bypass Operation, each
UPS Module will transfer to the bypass static switch circuit simultaneously.
4. Re-transfer operation from UPS MMS Bypass Operation to UPS MMS
Inverter Operation will be inhibited if any of the systems UPS Modules are