b. Inverter DC input varies from maximum to minimum.
c. Environmental condition variations within the specifications defined
herein.
G. Output Harmonic Distortion
The inverter output shall limit the amount of harmonic content to 2% maximum
at 100% linear load, and 5% maximum at 100% non-linear load. The need for
additional filtering to limit the harmonic content shall not be required. Therefore
high efficiency, reliability and original equipment footprint are maintained.
H. Output Overload Capability
The inverter output shall be capable of providing an overload current while
maintaining rated output voltage (and voltage regulation) to:
1. 105% to 125% for 10 minute duration.
2. 126% to 150% for 1 minute duration.
The UPS Module Operation/Display panel LED indication will illuminate to
identify an overload condition. If the time limit associated with the overload
condition expires or the overload is in excess of the set current, the load power
shall be transferred to the bypass source without interruption.
I. Inverter Current Limit
The inverter output current shall be limited to 212% of rated load current. Two
current transformers in separate locations on the output (and operating
separately offering redundancy) shall be employed as means of current
sensing.
The inverter current limit protects inverter components from damage due to
excessive over-current (Excessive load, faults and reverse current)
J. Inverter Overload Protection
The inverter output shall utilize the electronic inverter current limiting for
protection against overload conditions (excessive overload, faults). The
inverter shall utilize a contactor to isolate its output from the critical bus and the
load transferred to the bypass source. The bypass static switch circuit shall be
sized to provide fault clearing. The inverter output isolation contactor shall be
located internal to the UPS module and shall be controlled by the internal UPS
Module control.
The DC input to the Inverter shall utilize fuses for overload protection. Inverter
fuses shall be fast acting semiconductor type to clear faults on the DC link.
K. Inverter Output Isolate
The inverter output contactor isolates the inverter from the load and bypass
source.
L. Line Drop Compensation
The inverter shall be provided with circuitry such that its output voltage rises
linearly with output current. The rise shall be required to achieve this function,
and it shall not interfere with other requirements of this specification. The