Specifications

98AEtypSMSspec_RevC.doc
8
Copyright © 2007, Mitsubishi Electric Power Products, Inc.
SP-0012 Rev. C 09/05/09
input current total harmonic distortion (THD) into the utility AC input source at nominal
voltage and rated load. The reflected input current shall typically not exceed 9% THD at
50 % load.
C. Automatic Input Power Walk-in
The rectifier logic and control circuit power walk in function enables delayed and timed
ramping of input current. Subsequent to energizing the rectifier input, initiation of the
power walk in function and current ramping shall be delayed by a maximum of 3600
seconds (every 1 second adjustable – default at 10 second). Upon initiation of the power
walk-in function, the ramping of current shall be timed to gradually increase the load
within 10 seconds. This function is included as standard in the rectifier control circuitry.
D. Input Overcurrent Protection
Converter input contactor, input fuses, and the input current limit control shall provide
rectifier protection against excessive input overload conditions.
E. Step Load Change Operation (0-100%)
In the occurrence of a 100% step load change, the UPS Module inverter shall draw
power only from the rectifier to provide the required load demand. The charger/booster
shall not be utilized and the system batteries will not be cycled at any time during a step
load change.
2.2.1.2 Charger/Booster
A. General
The charger/booster utilizes solid state Pulse Width Modulation (PWM) controlled
Insulated Gate Bipolar Transistors (IGBT). The charger switching frequency is 10kHz,
and the booster switching frequency 2kHz.
B. Battery Charge Current Limit
The charger logic and control circuit DC battery current limiting function enables
controlled battery charging. The battery charge current limit will control the recharge
current by reducing the rectifier/charger output when the set limit is reached. The
following battery current limit shall be provided as a minimum:
1. Battery charge current limit: 10% of battery Ah rate.
2. Maximum charge current: 13% ampere of UPS rated kVA.
(e.g. 13ADC maximum of 100kVA UPS)
C. Equalize Charge Timer
UPS Module logic and control shall provide an electronic equalize charge timer function
(0 to 50 hour selectable - default twenty-four (24) hour). Once activated the timer circuit
shall provide a high rate equalizing charge voltage to the system battery for the selected
time. The function can be manually activated and de-activated via the UPS Module LCD.
The level of equalizing voltage shall be equal to that stated by the battery manufacturer
(typically .04 to .08 VDC/cell higher than the specified float level). Upon completion of
the timer count, the converter output voltage shall return to the specified float voltage
(typically 2.25 to 2.27 VDC/cell). An Auto Equalize charge operation is also provided