Specifications

98AEtypSMSspec_RevC.doc
7
Copyright © 2007, Mitsubishi Electric Power Products, Inc.
SP-0012 Rev. C 09/05/09
2.1.6 DC input and Battery
1. Voltage: 480V DC nominal, 400V DC minimum.
2. Voltage ripple (normal operation): less than 2% of DC voltage.
A. The Battery System shall be sized to provide the specified back-up time to the
inverter when the UPS is supplying 100% rated load.
B. Each Battery System shall include a disconnect 600V DC circuit breaker to
facilitate isolation of UPS Module DC Input and the Battery System. The DC
Circuit breaker shall incorporate an UVT relay and auxiliary contact
connections to the UPS Module control for prevention of incorrect start up and
shutdown sequencing.
C. The battery system shall be capable of operating in an average ambient
temperature of 25°C, with excursions of 16°C to 32°C and shall be sized as
follows:
Float Voltage: 545V DC (2.25 to 2.27 V/cell)
Final Voltage: 400V DC (1.67 V/cell)
2.1.7 Efficiency
UPS Module
Capacity (kVA)
Battery to AC
(100% Load)
AC to AC
(100% Load)
100 0.935 0.935
150 0.935 0.935
225 0.930 0.930
300 0.935 0.935
375 0.935 0.935
500 0.940 0.940
750 0.940 0.940
2.2 COMPONENTS
UPS module shall be comprised of the following;
2.2.1 Hybrid Converter Section:
AC input, converter input contactor, converter input fuse, input harmonic filter, and hybrid
converter utilizing;
2.2.1.1 High Power Diode Bridge Rectifier
A. General
A high power diode bridge rectifier converts the utility AC input power into regulated DC
power that serves as the inverter input and also as dc charge power to the system
battery through the chopper/booster. An AC reactor and capacitor shall filter the
harmonic content of rectifier input.
B. Reflected Harmonic Content
The high power diode bridge rectifier shall typically not introduce more than 6% reflected