Specifications

98AEtypSMSspec_RevC.doc
5
Copyright © 2007, Mitsubishi Electric Power Products, Inc.
SP-0012 Rev. C 09/05/09
1.7.2 Maintainability
MTTR of the UPS shall not exceed 1 hour including time to replace components.
1.7.3 Factory Test
A. The manufacturer shall fully and completely test the system to assure compliance with
the specifications, before shipment.
B. All UPS units shall come equipped with one (1) factory test report included in the UPS
enclosure. The factory test report shall include the following:
1. Series / kVA
2. Serial Number
3. Date of test
4. Approved by / Inspected by / Tested by
5. Inspection of construction
6. Checking of wiring (Black/Red marking on each connection point)
7. Grounding Continuity
8. Insulation strength test
9. Control Circuit Operation
10. Measurement of steady state characteristics (Voltage/ current/ efficiencies)
11. Transient characteristics (0-100% step load, without batteries/ voltage fluctuation)
12. Overload Testing
13. Transfer switch operation
PART 2 PRODUCT
2.1 ELECTRIC CHARACTERISTICS
The UPS shall have the following electrical characteristics;
2.1.1 UPS Output Capacity
The 9800A Series UPS Module is available in the following sizes:
kVA kW
100 80
150 120
225 180
300 270
375 337.5
500 450
750 675
UPS Module output capacities are in accordance with the following power factors:
A. 100 kVA ~ 225 kVA 0.8 pf lagging
B. 300 kVA ~ 750 kVA 0.9 pf lagging
2.1.2 Battery Capacity
A. Discharge time to end voltage: ___ minutes at full load, 25 degrees C (77 degrees F).