Specifications

98AEtypSMSspec_RevC.doc
18
Copyright © 2007, Mitsubishi Electric Power Products, Inc.
SP-0012 Rev. C 09/05/09
and control signals. The capture duration will be for 10 cycles, 5 cycles pre trigger
and 5 cycles post trigger. The sampling frequency shall be 7.2kHz, therefore a
total of 120 samples per cycle will be taken. The captured data can be
downloaded to a PC and displayed on Mitsubishi Electric Software. The Software
allows selection of UPS Module Waveform, logic and control signals for display
and zoom functions. Waveform capture information assists service personnel for
troubleshooting and undertaking UPS Module failure root cause analysis.
B. Download Alarm and System Event log to PC.
2.2.8 (Option) Remote Status Alarm Panel
The UPS manufacturer shall offer a Remote Status Alarm Panel which shall not allow any
control over the UPS. The RSAP shall have, as standard equipment, a battery backup
feature allowing it to continue monitoring UPS status conditions during power outage
situations. Ride through shall be for a minimum of 8 hours. The RSAP shall act only as an
annunciation panel providing the following alarms/indications as a minimum:
a. Rectifier on
b. Load on Inverter
c. Load on Bypass
d. UPS Failure
e. Output Overload
f. UPS in battery back-up mode
g. Low battery while in back-up mode
2.2.9 (Option) DiamondSync
The UPS manufacture shall offer a Sync circuit which shall allows any two or more
different UPS modules to sync into a master Sync source. The circuit allows both UPS
modules to operate in to a common output transfer cabinet and allows the load continue to
operate without any degradation to the load.
2.2.10 (Option) Common Battery
The customer is to advise if each UPS module is to have its own dedicated smaller battery
bank or if one large battery bank is required to operate the entire load.
2.3 MECHANICAL DESIGN
2.3.1 Cabinet Structure (Enclosure)
A. The enclosure shall be primed and painted with the Munsell 5Y7/1 (beige) color. The
enclosure shall be free standing floor mount design. The enclosure panels and doors
shall consist of minimum 14 gage steel for maximum strength and durability.
B. The UPS shall be installed in cabinets of heavy-duty structure meeting with NEMA
standard for floor mounting. The UPS shall be equipped with standard forklift
provisions to allow ease of installation using conventional lifting/moving equipment. The
UPS module cabinet shall have hinged and lockable doors on the front only. Operating
controls shall be located outside the locked doors. Input, output, and battery cables shall
be installed through the top or bottom of the cabinet.