Specifications

98AEtypSMSspec_RevC.doc
15
Copyright © 2007, Mitsubishi Electric Power Products, Inc.
SP-0012 Rev. C 09/05/09
f. Rectifier operation
g. Battery operation
h. Load on inverter
i. Inverter synchronized with bypass
j. Load on bypass
k. Equalize charge on
l. Alarm/Fault messages
Available operator sequence instructions:
a. Inverter start/stop
b. UPS start up/shutdown
c. Transfer of critical load to bypass source
d. Equalize charge to system battery
2. MEASUREMENT MENU Sheet: The MEASUREMENT MENU sheet indicates
details of measured values. The following data will be displayed on the
MEASUREMENT MENU Sheet:
a. Bypass Voltage and Frequency
b. Input Voltage and Frequency
c. Battery Voltage (and charge/discharge current)
d. Battery capacity remaining during power failure conditions
e. Output Power (kW)
f. Output Voltage (all phases including line to line and line to neutral)
g. Output Frequency
h. Output Current in RMS Amps and % (all phases including neutral).
3. SET UP MENU Sheet: The SET UP MENU Sheet prompts the user to select
specific performance and UPS setting data. (remote or local start & stop
operation, date & time adjustment, battery equalizing charge availability etc.)
4. LOG MENU Sheet: The LOG MENU Sheet indicates event and alarm/fault
information and battery discharge records. A maximum of 50 events can be
displayed. The following alarm/status information shall be available as a
minimum:
a. Load on Inverter
b. Battery Low Voltage
c. Battery Operation
d. Output Overload
e. Rectifier Operation
f. Inverter Running Synchronously
g. Static Bypass Input Out of Range
h. Minor Fault Data
i. Major Fault Data
2.2.5.2 LED indication
The Operation/Display Panel contains the following LED indication:
a. Load on Inverter (Green)
b. Battery operation (Yellow)
c. Load on Bypass (Green)
d. Overload (Red)