Specifications

98AEtypSMSspec_RevC.doc
13
Copyright © 2007, Mitsubishi Electric Power Products, Inc.
SP-0012 Rev. C 09/05/09
F. The UPS Module Control power supply employs a redundant design configuration,
utilizing the UPS AC input (utility) and the UPS Module inverter output therefore
enhancing reliability.
2.2.4 Bypass and Static Switch
UPS module contains an automatic bypass static switch circuit and associated bypass
static switch transfer control circuitry.
A. General
A bypass circuit shall be provided as an alternate source of power other than the inverter.
A high speed SCR switch and wrap-around contactor shall be used to assume the
critical load during automatic transfers to the bypass circuit. The static switch and
wrap-around contactor shall derive power from an upstream bypass feed contactor
internal to the UPS module. The wrap-around contactor shall be electrically connected in
parallel to the static switch and shall, at the same time as the static switch, be energized
and upon closure maintain the critical load feed from the bypass source. The static
switch shall only be utilized for the time needed to energize the wrap-around contactor
therefore increasing reliability. The bypass circuit shall be capable of supplying the
UPS rated load current and also provide fault clearing current capabilities. The UPS
system logic shall employ sensing which shall cause the static switch to energize within
150 microseconds therefore providing an uninterrupted transfer to the bypass source
when any of the following limitations are exceeded:
1. Inverter output undervoltage or overvoltage.
2. Overloads beyond the capability of the inverter.
3. DC circuit undervoltage or overvoltage.
4. Final voltage of system battery is reached (bypass source present and available).
5. System failure (e.g.: logic fail, fuse blown, etc.).
B. Automatic Re-transfers
In the event that the critical load must be transferred to the bypass source due to an
overload, the UPS system logic shall monitor the overload condition and, upon the
overload being cleared, perform an automatic re-transfer back to the inverter output.
The UPS system logic shall only allow a re-transfer to occur three times within a one
minute period. Re-transfers shall be inhibited on the fourth transfer due to the likelihood
of a recurring problem at the UPS load distribution. All retransfers will be inhibited if the
inverter and static bypass line are not synchronized.
C. Manual Transfers
The UPS shall be capable of transferring the critical load to/from the bypass source via
the front control panel. If performing manual transfers to inverter or automatic
retransfers, the UPS system logic shall force the inverter output voltage to match the
bypass input voltage and then parallel the inverter and bypass sources providing a
make-before-break transition allowing a controlled walk-in of load current to the inverter.
Manual transfers will be inhibited if the inverter and static bypass line are not
synchronized.
D. Static Switch