Specifications
98AEtypSMSspec_RevC.doc
11
Copyright © 2007, Mitsubishi Electric Power Products, Inc.
SP-0012 Rev. C 09/05/09
within +/-5% of the nominal value.
D. Voltage Transient Response
The dynamic regulation and transient response shall not exceed +/-2% for 100% step
load (applied or removed), +/-1% for loss or return of AC input and +/-5% for inverter to
bypass and vice versa transfer.
E. Transient Recovery
Voltage transient response shall not exceed the above specification and shall recover to
within nominal voltage regulation tolerance within 16.7 ms
F. Frequency Control
The Inverter output frequency shall be controlled by an oscillator internal to the UPS
module logic. It shall be capable of synchronizing to an external reference (e.g.; the
bypass source) or operating asynchronously. A message located on the touch screen
shall identify the loss of synchronization. Synchronization shall be maintained at 60 Hz
+/- 0.05% continuously. The Inverter output frequency shall not vary during steady
state or transient operation due to the following conditions:
1. 0 to 100% loading.
2. Inverter DC input varies from maximum to minimum.
3. Environmental condition variations within the specifications defined herein.
G. Output Harmonic Distortion
The inverter output shall limit the amount of harmonic content to 2% maximum at 100%
linear load, and 5% maximum at 100% non-linear load. The need for additional filtering
to limit the harmonic content shall not be required. Therefore high efficiency, reliability
and original equipment footprint are maintained.
H. Output Overload Capability
The inverter output shall be capable of providing an overload current while maintaining
rated output voltage (and voltage regulation) to:
105% to 125% for 10 minute duration.
125% to 150% for 1 minute duration.
The UPS Module Operation/Display panel LED indication will illuminate to identify an
overload condition. If the time limit associated with the overload condition expires or the
overload is in excess of the set current, the load power shall be transferred to the bypass
source without interruption.
I. Inverter Current Limit
The inverter output current shall be limited to 212% of rated load current. Two current
transformers in separate locations on the output (and operating separately offering
redundancy) shall be employed as means of current sensing.
The inverter current limit protects inverter components from damage due to excessive
over-current (Excessive load, faults and reverse current)










