Specifications

98AEtypSMSspec_RevC.doc
9
Copyright © 2007, Mitsubishi Electric Power Products, Inc.
SP-0012 Rev. C 09/05/09
following AC input restoration and subsequent to the power walk in function. This
equalizing charge will occur until the battery target voltage is reached (condition is met
to end equalizing charge), in which float voltage will be applied.
D. Battery Temperature Compensation
The UPS shall have as standard a battery temperature compensation function allowing
the rectifier voltage to fold-back to a safe value in the event the battery system
temperature reaches a pre determined (dangerous) level. Initiation will be by dry contact
input from thermocouple sensor (User supplied)
E. DC Input protection
The DC input circuit shall be protected by a DC circuit breaker. The DC circuit breaker
allows complete interruption of DC current and isolation of the UPS Module DC input
and the battery system.
The DC Circuit breaker shall incorporate an UVT relay and auxiliary contact connections
to the UPS Module control for prevention of incorrect start up and shutdown sequencing.
The DC Circuit Breaker shall be provided as standard equipment.
F. Charger/Booster protection
The DC input to the Charger/Booster shall utilize fuses for overload protection. The
fuses shall be fast acting semiconductor type to clear faults on the DC link.
G. Ripple voltage
The DC (battery) bus RMS ripple voltage shall be less than 2% of the UPS nominal DC
voltage level at 100% load. This shall provide for maximum battery life.
H. Battery Self Test (Diamond-Sense)
For a short duration, a small power discharge from the battery is automatically
performed. The UPS module, from this small power discharge, evaluates the
degradation of the system battery. The following advantages are achieved:
1. The Diamond-Sense Battery Self-Test function can be performed even when load
is on inverter.
2. Due to the short duration small power discharge, there is no effect to battery life
expectancy.
3. The small power discharge has negligible effect on the overall battery back up time.
The small power that is discharged by the battery will quickly be replenished.
The Battery Self Test will automatically occur every 720 hour interval. An event alarm will
occur and be displayed if battery abnormalities are detected.
2.2.1.3 Input Current Limit
The rectifier and booster logic and control shall provide an input current limiting function
that limits AC input current. Two current transformers in separate locations on the output
(and operating separately offering redundancy) shall be employed as means of current
sensing.