Graphic Operation Terminal F930GOT Introduction 1
1-29
• Connection diagram
Connect the GOT to the host unit as shown below.
* Control lines RTS, CTS, DTR and DSR are not used.
• Communication setting
The setting related to communication can be performed using the screen creation software
or the GOT main body. (As to the screen creation software, refer to the operation manual of
the software.)
To use general-purpose communication, select "SET-UP MODE", "PLC TYPE" and "UNI-
VERSAL" in this order in the GOT main body.
To set the communication speed (baud rate), the data length, the stop bit length and the
parity, select "SET-UP MODE" and "SERIAL PORT (RS-232C)" in this order in the GOT
main body.
Set each parameter to an either available value shown below.
Table 1.15:
Baud rate 19,200, 9,600, 4,800, 2,400, 1,200, 600 or 300 (bps)
Data length 8 or 7bits
Stop bit length 1 or 2bits
Parity Even, odd or none
Host unit side
FG
SD
RD
SG
➀
➁
➂
➆
➇
➅
➃
➄
GOT
side
D-sub
(female),
9-pin
5
4
3
2
1
9
8
7
6