User`s manual
Graphic Operation Terminal F930GOT Introduction 1
1-22
When the GOT is connected to the SYSMAC C Series PLC manufactured by OMRON, the fol-
lowing setting is required.
• Setting of host link unit
Set the communication format of the host link unit as shown below.
Only a model in which these set items are offered can be connected to the GOT.
Setting example:
Set the communication format while referring to setting examples of each C Series host link unit.
In the case of CQM1-CPU : Setting by data memory (DM)
In the case of host link unit attached to C200H base :
Setting by each switch (when C200H-LK201-V1/C200H-LK202-V1 is used)
- Setting of switches on front face
(common between C200H-LK201-V1 and C200H-LK202-V1)
*1 Equivalent to station No. setting in the GOT
Table 1.5:
Used port When RS-422 is used When RS-232C is used
Transmission speed 19200 bps
Data bit 7 bits
Stop bit 2 bit
Parity bit Even
Communication mode Host link mode
Command level Level 1, 2 or 3
Procedure 1:N procedure
Unit No. 00 to 15 (BCD) (in accordance with setting in GOT)
↑
The GOT station No. can be set in "SET-UP MODE". (Refer to Paragraph 2.2.)
Table 1.6:
Set item Set item Remarks
Standard communication con-
dition (RS-232C: DN6645)
0001H
Mode specification: Host link
Communication condition: In accordance with DM6646
Communication condition
(RS-232C: DM6646)
0304H
Transmission format: 7 data bits and 2 stop bits
Parity: Even Transmission speed: 19,200 bps
Send delay time
(RS-232C: DM6647)
0000H
(initial status)
0 second
Unit No. (RS-232C: DM6648) 00
××
H
××
: Two-digit BCD (in accordance with setting in GOT)
Table 1.7:
Set item Switch setting Remarks
Unit No.
SW1 *1 Upper digit BCD
SW2 *1 Lower digit BCD
Transmission speed SW3 6 19200 bps
Communication condition SW4 2
7 ASCII bits and 2 stop bits
Parity: Even Command level: 1, 2 or 3