When the GOT is connected to the MELSEC A Series PLC via a computer link unit, the follow-
ing setting is required.
Setting of computer link unit
Set the communication format of the computer link unit as shown below.
Caution: When RS-232C is connected
The GOT does not control CD signals. Accordingly, when the RS-232C is connected, the
buffer memory in the computer link unit should be set so that CD signals are not checked.
Example: When I/O signals in the computer link unit are 80 (H) to 9F (H)
Restriction in functions
In connection via computer link unit, the following functions of the GOT are disabled.
- Index registers (V and Z) cannot be monitored, and their current values cannot be
changed.
- When the RS-232C is connected for communication, the printer output function of the
GOT is disabled.
- The two-port interface function is disabled.
Table 1.4:
Used port When RS-422 is used When RS-232C is used
Mode setting switch No.
5
RS-422: Format 1
RS-232C: No-procedure
1
RS-422: No-procedure
RS-232C: Format 1
Transmission speed 19200 bps
Data bit 7 bits
Stop bit 1 bit
Parity bit Even
Sum check Provided
Write during run Possible
Station No. 00 to 0F (in accordance with setting in GOT)
The GOT station No. can be set in "SET-UP MODE". (Refer to Paragraph 2.2.)
X87
P
TO
H8 H10B K1 K1
Write to buffer memory
Computer link unit connection point
10B (H): CD terminal will be checked.
K1: CD terminal will not be checked.