User`s manual

Graphic Operation Terminal F930GOT Additional Functions (V 2.20/3.00 or later) 15
15-10
15.5 Additional function to connect two or more GOT units when micro computer
boards are used
In the GOT unit V 3.00 or later, up to four GOT units can be connected at a time when micro
computer boards (for general-purpose communication) are used.
(For connection on the one-to-one basis, refer to Paragraph 1.6.6.)
15.5.1 Setting when two or more GOT units are connected
When GOT units and micro computer boards are connected on the one-to-one basis
Connection type
Perform either one among the followings.
- When using the screen creation software (DU/WIN-E), set "PLC System" to "Universal".
- When using the screen creation software (GOTRE-PACK), set the PLC type to "My Com-
puter".
- When using the GOT unit main body, select "SET-UP MODE" -> "PLC TYPE", and select
"UNIVERSAL".
Setting of communication port
Perform either one between the followings.
- When using the screen creation software (DU/WIN-E), select "View"
"System Set-
tings"
"Setup Data", then set the port to "RS232C" or "RS422".
- When using the GOT unit main body, select "SET-UP MODE"
"PLC TYPE", and set
"CONNECTION" to "CPU PORT (RS232C)" or "CPU PORT (RS422)".
When using the screen creation software (GOTRE-PACK), you cannot set the communica-
tion port.
Setting of communication speed, data length, stop bit length and parity bit
- When using the screen creation software (DU/WIN-E), select "View"
"System Set-
tings"
"DU Printer".
- When using the GOT unit main body, select "SET-UP MODE"
"SERIAL PORT".
When using the screen creation software (GOTRE-PACK), you cannot set the communica-
tion condition.
For each set item, select an either value among those shown below.
Setting when two or more GOT units are connected
When two or more GOT units are connected, you should set the station No. for each GOT unit.
Perform either one between the followings.
- When using the screen creation software (DU/WIN-E), select "View"
"System Set-
tings"
"Setup Data", then set the station No.
- When using the GOT unit main body, select "SET-UP MODE"
"PLC TYPE", then set
"STATION #".
When using the screen creation software (GOTRE-PACK), set the station No. using the
GOT unit main body.
Table 15.13:
Transmission speed 19200, 9600, 4800, 2400, 1200, 600, 300 (bps)
Data length 8 or 7 bits
Stop bit length 1 or 2 bits
Parity bit Even, odd or none