User`s manual
Graphic Operation Terminal F930GOT Additional Functions (V 2.20/3.00 or later) 15
15-7
15.4 Connection to machine controller manufactured by YASUKAWA ELECTRIC CORP.
15.4.1 Direct connection to CPU
• Connected PLC
Direct connection to CPU (RS-232C or RS-422)
- Applicable machine controller
• Setting of machine controller
Set the machine controller as shown below.
• Setting of GOT
Set the connected PLC, the connection type and the station No. as shown below.
• System configuration
Table 15.8:
Model Condition
CP9200SH • CN1, CN2, CN3 of MEMOBUS unit 217F
MP920
• MEMOBUS port PORT1, PORT2 of CPU unit
• CN1, CN2, CN3 of MEMOBUS unit 217F
MP930 • MEMOBUS port PORT1, PORT2 of CPU unit
Table 15.9:
Item Set value
Protocol MEMOBUS
Mode RTU
Communication speed 19,200bps
Data length 8 bits
Stop bit length 1 bit
Parity bit Even
Slave address 1 to 31 (in accordance with station No. setting in GOT)
Table 15.10:
PLC TYPE CP9200SH manufactured by YASUKAWA
CONNECTION CPU PORT (RS-232C) or CPU PORT (RS-422)
STATION #
In accordance with slave address of machine controller.
Make sure to set station No. inside range from 1 to 31.
Have in mind that station No. "0" is treated as "1".
In case of CPU unit
(MP920, MP930)
Machine controller
In case of MEMOBUS unit
(CP9200SH, MP920)
GOT
RS-232C(MEMOBUS)
RS-232C or RS-422 (MEMOBUS)
MEMOBUS unit 217F