User`s manual

Graphic Operation Terminal F930GOT Additional Functions (V 2.20/3.00 or later) 15
15-7
15.4 Connection to machine controller manufactured by YASUKAWA ELECTRIC CORP.
15.4.1 Direct connection to CPU
Connected PLC
Direct connection to CPU (RS-232C or RS-422)
- Applicable machine controller
Setting of machine controller
Set the machine controller as shown below.
Setting of GOT
Set the connected PLC, the connection type and the station No. as shown below.
System configuration
Table 15.8:
Model Condition
CP9200SH • CN1, CN2, CN3 of MEMOBUS unit 217F
MP920
• MEMOBUS port PORT1, PORT2 of CPU unit
• CN1, CN2, CN3 of MEMOBUS unit 217F
MP930 • MEMOBUS port PORT1, PORT2 of CPU unit
Table 15.9:
Item Set value
Protocol MEMOBUS
Mode RTU
Communication speed 19,200bps
Data length 8 bits
Stop bit length 1 bit
Parity bit Even
Slave address 1 to 31 (in accordance with station No. setting in GOT)
Table 15.10:
PLC TYPE CP9200SH manufactured by YASUKAWA
CONNECTION CPU PORT (RS-232C) or CPU PORT (RS-422)
STATION #
In accordance with slave address of machine controller.
Make sure to set station No. inside range from 1 to 31.
Have in mind that station No. "0" is treated as "1".
In case of CPU unit
(MP920, MP930)
Machine controller
In case of MEMOBUS unit
(CP9200SH, MP920)
GOT
RS-232C(MEMOBUS)
RS-232C or RS-422 (MEMOBUS)
MEMOBUS unit 217F