User`s manual
Graphic Operation Terminal F930GOT Additional Functions (V 2.20/3.00 or later) 15
15-5
Cable 6ES7901-1BF00-0XA0 manufactured by Siemens is available also.
15.3.2 Support device range list
✰
Word devices are shaded, and bit devices are not shaded.
*1 Notation used in the GOT
The device specification method is partially different. Refer to the next paragraph.
15.3.3 Device specification method and restraint in GOT
• Device specification method
Specify devices in the following formats.
1) Bit device
¨¨¨¨
✰
• In "
", specify the device symbol (shown in Table 1) in one alphabet.
•In "
¨¨¨¨
", specify the device No. (shown in Table 1) of the specified device in a deci-
mal value in three or four digits.
•In "
✰
", specify the bit position. The available range is from 0 to 7.
Example: When specifying "M01205"
Device symbol = M
Device (byte) No. = 120
Bit position = 5
2) Timer (T) and counter (C)
The specification method is equivalent to that for bit devices except that the bit position (
✰
)
is omitted.
Example: When specifying "T250"
Device symbol = T
Device No. = 250
Table 15.7: Support device range list
Device name (symbol)
Available setting range
Notation in PLC
Notation in GOT
*1
Input relay (I) I0.0 to I511.7
←
Output relay (Q) Q0.0 to Q511.7
←
Bit memory (M) M0.0 to M2047.7
←
Timer current value (T) T0 to T511
←
Counter current value (C) C0 to C511
←
Data register (D)
DB1.DBW0 to DB1.DBW65534
DB2.DBW0 to DB2.DBW65534
•
DB1023.DBW0 to DB1023.DBW65534
D000100000 to D000165534
D000200000 to D000265534
•
D102300000 to D102365534
GOT side
D-sub
(female),
9-pin
connector
HMI adapter
side (PLC side)
D-sub
(female),
9-pin
connector
➁
➂
➃
➄
➅
1
2
3
4
5
6
7
8
9
➆
1
2
3
4
5
6
7
8
9
➀
➇
➁
➂
➃
➄
➅
➆
➀
➇
CD(DCD)
RD(RXD)
SD(TXD)
ER(DTR)
SG(GND)
DR(DSR)
RS(RTS)
CS(CTS)