User`s manual
Graphic Operation Terminal F930GOT Additional Functions (V 2.20/3.00 or later) 15
15-4
15.3 Connection to PLC manufactured by Siemens
15.3.1 Direct connection to CPU
• Connected PLC
For direct connection to CPU (RS-232C), the HMI adapter is required. (Refer to the con-
nection example shown below.)
However, 416-1 and 416-2DP do not support some devices. (Refer to the next page.)
• Setting of PLC
Set the MPI address of the PLC connected to the GOT using the programming software
(STEP7) for the S7-300/400 Series PLC.
The MPI address of the HMI adapter is "1", and the maximum MPI address is "31". Accord-
ingly, make sure to set the MPI address of the PLC inside the range from 2 to 31.
• Setting of GOT
Set the connected PLC, the connection type and the station No. as shown below.
<Direct connection to CPU>
Table 15.4:
Applicable CPU
S7-300 Series 312IFM, 313, 314, 314IFM, 315, 315-2DP, 316
S7-400 Series 412-1, 413-1, 413-20DP, 414-1, 414-2DP, 416-1, 416-20DP
Table 15.5:
MPI address
Personal computer
(for programming)
0 (fixed in MPI network)
HMI adapter 1 (fixed)
PLC 2 to 31
Table 15.6:
PLC TYPE "SIMENS S7-300"
CONNECTION CPU PORT (RS232C)
STATION #
MPI address (2 to 31) set in PLC
Have in mind that station Nos. "0" and "1" are treated as "2".
CPU
HMI Adapter
MPI
Cable shown in wiring diagram
(RS-232C)
F930GOT
RS-232C connection
S7-300/400 Series manufactured by Siemens
HMI adapter model name: 6ES7 972-0CA11-0XA0 (manufactured by Siemens)