User`s manual

Graphic Operation Terminal F930GOT Additional Functions (V 2.20/3.00 or later) 15
15-2
15.2 Connection to MELSEC Q Series PLC
15.2.1 Direct connection to CPU
Applicable PLC: Q Series PLC
Connection type: Direct connection to CPU (RS-232C)
<Direct connection to CPU> RS-232C
15.2.2 Connection to serial communication unit
Applicable serial communication unit: QJ71C24, QJ71C24-R2
Connection type: Direct connection to CPU (RS-232C or RS-422)
Caution:
When connecting the GOT to a serial communication unit, select "direct connection to CPU"
as the connection type.
Though each of the QJ71C24 and the QJ71C24-R2 is equipped with two interface ports,
the GOT can be connected to only an either port.
Setting of serial communication unit
Set the communication format of the serial communication unit as shown below.
n
nn
n
Important point
Setting of screen creation software
SW
¨
D5C-GOTRE-PACK
From "
¨
= 2, Version 00A" to
¨
= 4, Version 30C": Set "PLC TYPE" to "A, QnA".
"
¨
= 4, Version 50F or later": Set "PLC TYPE" to "QnA, Q".
Table 15.3:
Used port When RS-422 is used When RS-232C is used
Communication
protocol
5
RS-422 : Format 5
RS-232C: No-procedure
5
RS-422 : No-procedure
RS-232C : Format 5
Transmission
speed
38400bps
Data bit length
8 bits
Stop bit length
1 bit
Parity bit
Provided (odd)
Sum check
Provided
Write during run
Possible
Station No.
00 to 0F (in accordance with setting in GOT)
The GOT station No. can
be set in "SET-UP MODE".
CPU Connection cable shown on the right
Connect the RS-232C connector of the GOT.
Cable: QC30R2 (3 m)