User`s manual
Graphic Operation Terminal F930GOT Additional Functions (in V.2.00 or later) 13
13-10
13.3.3 Device list
The table below shows the list of devices in the SLC500 Series compatible with the GOT.
And have in mind the restriction described below.
• Device specification method
Use the following format to specify bit/word devices.
1) Bit device
¡¡¡¨¨¨
-
: Specify the device symbol (shown in the table below) in one or two alphabets.
-
¡¡¡
:Specify the file No. (shown in the table below) corresponding to each device in
decimal(*1).
-
¨¨¨
:Specify the element (device No.) in decimal.
Example: To specify "B003064E"
Device symbol: B Element (device No.): 64
File No.: 3 Bit position: E
2) Word device
The specification method is equivalent to that for bit devices.
Example: To specify "N057129"
Device symbol: N Element (device No.): 129
File No.: 57
*1 The file Nos. 10 to 255 are required to be set in advance using the package software
manufactured by Allen-Bradley.
• Support device table
Note: Shaded columns indicate word devices. Other columns indicate bit devices.
Device name (symbol)
File No.
¡¡¡
Available element (device No.)
specification range
¨¨¨
Bit (B)
3, 10 to 255 0 to 255
Timer coil (TT)
4, 10 to 255 0 to 255
Timer contact (TN)
4, 10 to 255 0 to 255
Timer set value (TP)
4, 10 to 255 0 to 255
Timer current value (TA)
4, 10 to 255 0 to 255
UP counter coil (CU)
5, 10 to 255 0 to 255
DOWN counter coil (CD)
5, 10 to 255 0 to 255
Counter contact (CN)
5, 10 to 255 0 to 255
Counter set value (CP)
5, 10 to 255 0 to 255
Counter current value (CA)
5, 10 to 255 0 to 255
Integer (N)
7, 10 to 255 0 to 255