11.4.3 Bar graph
The "Bar" object displays a word device in the PLC in the form of bar graph.
A numeric which is rather difficult to understand in the form of number can be displayed in the
form of bar graph so that it can be easily understood at a glance.
u
uu
u
Contents of setting
Display direction : Vertical or horizontal
Monitored device : Word device (T, C, D or GD)
Number of ticks : 2 to 11
Color : Graph color, frame color and scale color
• Bar graph type: Horizontal (left -> right) or vertical (down -> up)
• The entered minimum value is regarded as 0%, and the entered maximum value is
regarded as 100%. The acquired data is represented in % against 100%.
If the acquired data is larger than the maximum value or smaller than the minimum value, a
diagonal line is drawn in the bar graph.
The bar graph is displayed from the specified reference value position.
Word Device: D1
Maximum Value: 3000
Minimum Value: 1000
Reference value:1000
D1 1500 D1 0
Minimum Value
(1000)
Current value of
word device
(1500 = 25%)
Maximum Value
(3000)
(When the value of the word device is
smaller than "Minimum Value)
Graph Type: Right (left right)
Graph Type: Up (down up)
Maximum Value
Minimum
Value
Current value of
word device
Ticks
Ticks
à