Installation manual
2 Specifications
2.1 General Specifications
E
CAUTION:
Please operate the Graphic Operation Terminal in the listed conditions only.
If the GOT is used under other conditions, electric shock, fire, malfunction, damages
or deterioration may be caused.
Specifications
8 MITSUBISHI ELECTRIC
Item Specifications
Operating ambient
temperature
0 to +50 °C
Storage ambient
temperature
-20 to +60 °C
Ambient humidity for opera
-
tion and storage
35 to 85 % relative humidity, non-condensing
Vibration resistance
Conforms to
IEC61131-2
Intermittent Vibration
Frequency Acceleration
Amplitude
(half)
Sweep count for
X, Y, Z
10 to 57 Hz — 0,075 mm
10 times
(80 minutes in
each direction)
57 to 150 Hz 9,8 m/s
2
(1 g) —
Continuous Vibration
10 to 57 Hz — 0,035 mm
57 to 150 Hz 4,9 m/s
2
(0,5 g) —
Shock resistance Conforms to IEC61131-2, 147 m/s
2
(15 g), 3 times in each direction X, Y und Z
Noise immunity 1000 Vp-p tested by noise simulator, 1 µs at 30 to 100 Hz
Dielectric withstand voltage
500 V AC > 1 min., tested between power terminals and ground
(For F920GOT-BBD5-K-E only: between all power terminals of the PLC and ground
terminal)
Insulation resistance
5 MΩ at 500 V DC, tested between power terminals and ground
(For F920GOT-BBD5-K-E only: between all power terminals of the PLC and ground
terminal)
Grounding
Class D grounding (Grounding resistance 100 Ω or less), If grounding is impossible,
it can be omitted.
Operating environment No dust, soot, corrosive or conductive dust, corrosive or flammable gas
Protection IP65