EXT DIAGNOSTIC
Range: 0 to FFFF
(External Diagnostic) The value of this parameter appears as the 2nd and 3rd bytes of the
application specific diagnostics to the master. Refer to “PROFIBUS Diagnostics”, page 20. This
provides a simple way to implement user defined trips or exceptions.
INT DIAG SELECT
Range: 0 to 29999
(Internal Diagnostic Select) Refer to “Internal Diagnostics”, page 22.
UNUSED 1
Range: 0 to FFFF
Reserved for future use.
UNUSED 2
Range: 0 to FFFF
Reserved for future use.
FAULT
Range: Enumerated - see below
The fault state of the Technology Option.
0 : NONE no faults
1 : PARAMETER parameter out-of-range
2 : TYPE MISMATCH TYPE parameter not set to PROFIBUS DP
3 : SELF TEST hardware fault - internal
4 : HARDWARE hardware fault - external
5 : MISSING no option fitted
Also refer to Network and Module LED Indications, page 9.
VERSION
Range: 0000 to FFFF
The version of the Technology Option card. If no option is fitted then the version is reset to zero.
NETWORK STATE
Range: Enumerated - see below
The network state of the Technology Option card. Refer to “Network and Module LED
Indications” page 9 for further information.
Enumerated Value : Fault State
0 : DATA EXCHANGE
1 : DATA EX ERROR
2 : WAIT CONFIG
3 : WAIT PARAM
4 : BAUD SEARCH
5 : DISABLED
DATA EXCHANGE
Data Exchange mode. The parameterisation and configuration have been accepted and the slave
is exchanging user data with the master.
DATA EX ERROR
Data Exchange mode, as above, but with read/write error(s). This indicates that at least one of the
parameters being read or written is failing, for example writing a value out of range.
WAIT CONFIG
Waiting for configuration. The parameterisation from the master has been accepted and is now
waiting for the Master to send valid configuration data.
WAIT PARAM
Waiting for parameterisation. The slave has detected communications at a valid baud rate and is
waiting for the master to send valid parametrisation data.
BAUD SEARCH
The slave has not detected valid communications.
DISABLED
The interface is disabled. The reason for this is given by the FAULT parameter.
INT DIAGNOSTIC
Range: 0000 to FFFF
Refer to “Internal Diagnostics”, page 22.