Specifications
2033D Specification
12
the static switch to energize immediately thus providing an uninterrupted transfer
to the bypass source when any of the following limitations are exceeded:
a. Inverter output undervoltage or overvoltage.
b. Overloads beyond the capability of the inverter.
c. DC circuit undervoltage or overvoltage.
d. Final voltage of system battery is reached (bypass source present and
available).
e. System failure (e.g.: logic fail, fuse blown, etc.).
4.3.2 Automatic Re-transfers
In the event that the critical load must be transferred to the bypass source due to an
overload, the UPS system logic shall monitor the overload condition and, upon the
overload being cleared, perform an automatic re-transfer back to the inverter
output. The UPS sy stem logic shall only allow a re-transfer to occur three times
within a one minute period. Re-transfers shall be inhibited on the fourth transfer
due to the likely hood of a recurring problem at the UPS load distribution. The re-
transfer of load to the inverter shall also be inhibited due to the limitations set in
section 3.3. All retransfers will be inhibited if the inverter and static bypass line
are not synchronized.
4.3.3 Manual Transfers
The UPS shall be capable of transferring the critical load to/from the bypass
source via the front control panel. . If performing manual transfers to inverter or
automatic retransfers, the UPS system logic shall force the inverter output voltage
to match the bypass input voltage and then parallel the inverter and bypass sources
providing a make-before-break transition allowing a controlled walk -in of load
current to the inverter. Manual transfers will be inhibited if the inverter and static
bypass line are not synchronized.
4.3.4 Static Switch
The static switch shall be a high speed transfer device comprised of naturally
commutated SCR's.
5. OPERATOR CONTROL PANEL
5.1 Operator Controls
The operator control panel shall employ the use of a touch screen interface which allows
lock-out of all UPS control functions for security (the Emergency Power Off function shall
not be locked-out). The operator interface shall provide the following: