Specifications
2033D Specification
11
The Inverter output shall be capable of providing an overload current while
maintaining rated output voltage to the values stated in section 3.4.10. A message
indicating LED located on the control panel shall illuminate to identify this
condition. If the time limit associated with the overload condition expires or the
overload is in excess of the set current amplitude, the load power shall be
transferred to the bypass source without interruption.
4.2.6 Inverter Current Limit
The Inverter output shall also be limited to 150% of rated load current. The two
sensing locations shall operate separately and independently thus providing
redundancy and, in the event of a failure, prevent unnecessary damage to power
transistor components/fuses. Load current above 150% shall cause an immediate
transfer of the load to the bypass source for fault clearing.
4.2.7 Inverter Overload Protection
The Inverter AC output shall utilize electronic current limiting for overload
conditions. The Inverter shall utilize a contactor to isolate its output from the
critical bus.
a. The Inverter fuses shall be the fast acting semiconductor type to clear
faults on the AC buss.
b. The Inverter output isolation contactor shall be located internal to the UPS
module and shall be controlled by the internal UPS module system logic.
4.2.8 Line Drop Compensation
The inverter shall be provided with circuitry such that its output voltage rises
linearly with output current. The rise shall be required to achieve this function, and
it shall not interfere with other requirements of this specification. The purpose of
this feature is to compensate for varying line drop voltage between the inverter and
the critical load.
4.3 Bypass and Static Switch
4.3.1 General
A bypass circuit shall be provided as an alternate source of power other than the
inverter. A high speed SCR switch shall be used to assume the critical load during
automatic transfers to the bypass circuit. The static switch shall derive power from
an upstream bypass feed contactor internal to the UPS module. The bypass circuit
shall be capable of supplying the UPS rated load current and also provide fault
clearing current. The UPS s ystem logic shall employ sensing which shall cause