AIR-COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS DATA BOOK Series : PE(H) Cooling only Heat pump Model PE-7MYC PE-8MYC PE-10MYC PE-15MYC PE-20MYC Service ref.
CONTENTS SAFETY FOR USE ------------------------------------------------------2 A COMPLETE LINE UP ------------------------------------------------4 FEATURES-----------------------------------------------------------------5 DESCRIPTIONS----------------------------------------------------------5 MECHANICAL SPECIFICATIONS ----------------------------------6 TYPICAL INSTALLATION EXAMPLE ------------------------------6 MODEL-DESIGNATION BREAKDOWN ---------------------------7 SPECIFICATIONS ---------------------
SAFETY FOR USE Before conducting installation work, please read this ''SAFETY FOR USE'' carefully for correct installation. Since the caution items shown here contain important description relative to safety, please observe them without fail. Warning Erroneous handling gives a high possibility to induce serious results such as death or heavy injury. Caution Erroneous handling may induce serious injury depending on the situation.
Caution Arrange the configuration of wiring not to bring up the panel and terminal cover, and fasten the panel and terminal cover securely. The poor mounting of the panel or terminal cover may cause the heat generation of the terminal connection, a fire or electrical shock. Never install on the place where a combustible gas might leak. The gas may ignite or explode when the gas leaks and collects in surround of the unit.
A COMPLETE LINE UP Cooling capacity Heating capacity (PEH only) PEH-5 PE(H)-7 PE(H)-8 PE(H)-10 PE-15/PEH-15 PE(H)-20 kW 14.4 17.9 22.0 28.8 47.0/44.0 57.6 Btu/h 49,150 61,100 75,100 98,300 160,400/150,200 196,600 kcal/h 12,400 15,400 18,900 24,800 40,500/37,900 49,500 kW 14.4 18.8 22.0 28.8 44.0 57.
FEATURES Highly efficient operation Labour saving installation The EER(Energy Efficiency Ratio) on these models is greatly improved by revised design specifications and by being manufactured stringently to Mitsubishi Electric high quality standards. The unit operation can commence immediately after connecting to the power supply, refrigerant piping, drain piping, ducting and control system.
MECHANICAL SPECIFICATIONS General Condenser Coils All units are factory assembled, piped, internally wired. They are also tested and checked under a strict quality control system in the factory. Exterior surfaces of all units of outdoor unit are phosphatized, zinc-coated steel with powder coating and ivory white baked enamel finish. Unnecessary power input due to higher discharge pressure is avoided by high performance designs of cross-finned coil. Condenser coils are made of 9.52mm OD, 0.
MODEL-DESIGNATION BREAKDOWN P E - 10 M Y C 1 Service reference Design Sequence Electrical Supply Y = 3 phase 380~415V 50Hz 4 wires of PE(H)-7 Indoor unit ( InY =case 1 phase 220~240V 50Hz 2 wires ) Compressor Horsepower 5 = 5 HP 7 = 7 HP 8 = 7.
SPECIFICATIONS Cooling only PE-7~20MYC PE-7MYC PE-8MYC PE-10MYC PE-15MYC PE-20MYC PE-7MYC-EU PE-8MYC-EU PE-10MYC-EU PE-15MYC1-EU PE-20MYC-EU kW Btu/h kcal/h 17.9 61,100 Sensible cooling capacity (Gross) kW Btu/h kcal/h 14.3 48,800 22.0 75,100 18,900 17.6 60,100 15,100 28.8 98,300 24,800 23.0 78,500 19,800 47.0 160,400 40,400 37.6 128,300 32,300 57.6 196,600 49,500 46.1 157,300 39,600 Total cooling capacity (Net) kW Btu/h kcal/h 17.2/17.1 58,700/58,300 21.4 73,000 18,400 27.
PEH-5,7,8MYA Model name Service reference Total cooling capacity (Gross) Heat pump kW Btu/h kcal/h Sensible cooling capacity (Gross) kW Btu/h kcal/h Total cooling capacity (Net) kW Btu/h kcal/h Heating capacity (Gross) kW Btu/h kcal/h Heating capacity (Net) kW Btu/h kcal/h Power supply Indoor Outdoor Capacity step Refrigerant Refrigerant charge Refrigerant control Indoor Unit Model name PEH-7MYA PEH-8MYA PEH-5MYA-EU PEH-7MYA-EU PEH-8MYA-EU 14.4 49,100 12,400 11.5 39,200 9,900 13.
PEH-10,15,20MYA Heat pump Model name Service reference Total cooling capacity (Gross) kW Btu/h kcal/h Sensible cooling capacity (Gross) kW Btu/h kcal/h kW Btu/h kcal/h Total cooling capacity (Net) Heating capacity (Gross) kW Btu/h kcal/h Heating capacity (Net) kW Btu/h kcal/h Power supply PEH-15MYA PEH-20MYA PEH-10MYA-EU PEH-15MYA-EU PEH-20MYA-EU 27.8 94,900 23,900 27.8 94,900 23,900 27.8 94,900 44.0 150,200 37,900 35.2 120,200 30,200 42.5/41.7 145,000/142,300 36,600/35,900 41.
ELECTRICAL DATA PE-7~20MYC-EU Cooling VOLT PE-7 240V PE8~20 415V PE-7 230V PE8~20 400V PE-7 220V PE8~20 380V ITEM PE-7MYC-EU PE-8MYC-EU PE-10MYC-EU PE-15MYC1-EU PE-20MYC-EU PU-7MYC1-EU PU-8MYC1-EU PU-10MYC1-EU PU-15MYC1-EU PU-20MYC1-EU 17.4/17.6 10.1 7.8 21.1/22.0 7.1/7.2 29.1/29.6 19.0 14.2 37.3/39.1 14.2/14.6 83 74 76 78 119 82 83 140 74 2 × 9.2 2 × 7.65 8.6 6.8 6.0 ×15.95 2 16.0 12.3 10.7 2 × 12.
PEH-5,7,8MYA-EU Cooling VOLT ITEM TOTAL INPUT TOTAL RUN CURRENT POWER FACTOR START CURRENT PEH-7 240V COMPRESSOR INPUT RUN CURRENT PEH- INDOOR side 5, 8 External static pressure 415V INDOOR FAN INPUT kW A % A kW A PEH-5MYA-EU PEH-7MYA-EU PEH-8MYA-EU PUH-5MYE1-EU PUH-7MYC2-EU PUH-8MYC2-EU PUH-8MYE1-EU 7.8 7.9 5.49 7.1/7.2 14.2 14.7 9.6 14.2/14.6 76 75 80 83 83 69 74 6.8 6.8 4.7 6.0 12.3 12.3 8.1 10.7 Pa 50/125 50/125 62/125 62/125 RUN CURRENT OUTDOOR FAN INPUT RUN CURRENT kW A kW A 0.54 1.0 0.
PEH-5,7,8MYA-EU Heating VOLT ITEM TOTAL INPUT TOTAL RUN CURRENT POWER FACTOR START CURRENT PEH-7 240V COMPRESSOR INPUT RUN CURRENT PEH- INDOOR side 5, 8 External static pressure 415V INDOOR FAN INPUT kW A % A kW A PEH-5MYA-EU PEH-7MYA-EU PEH-8MYA-EU PUH-5MYE1-EU PUH-7MYC2-EU PUH-8MYC2-EU PUH-8MYE1-EU 6.5 4.5 6.6 6.2/6.3 12.4 8.6 12.9 13.2/13.6 73 73 71 83 69 83 74 5.5 3.71 5.5 5.1 10.5 7.1 10.5 9.7 Pa 50/125 50/125 62/125 62/125 RUN CURRENT OUTDOOR FAN INPUT RUN CURRENT kW A kW A 0.54 1.0 0.
PEH-10,15,20MYA-EU Cooling VOLT PEH10~20 415V PEH10~20 400V PEH10~20 380V ITEM PEH-10MYA-EU PEH-15MYA-EU PEH-20MYA-EU PUH-10MYC2-EU PUH-10MYE1-EU PUH-15MYC2-EU PUH-20MYC2-EU 16.1/16.9 10.1 10.2 20.8/21.8 29.5/30.9 19.0 19.3 37.4/39.3 76 74 74 77 119 82 82 140 2 × 9.15 2 × 6.8 8.6 8.7 2 × 16.1 16.0 16.1 2 × 12.
PEH-10,15,20MYA-EU Heating VOLT PEH10~20 415V PEH10~20 400V PEH10~20 380V ITEM PEH-10MYA-EU PEH-15MYA-EU PEH-20MYA-EU PUH-10MYC2-EU PUH-10MYE1-EU PUH-15MYC2-EU PUH-20MYC2-EU 13.7/14.5 8.3 8.6 16.2/17.2 25.5/26.9 16.1 16.4 31.3/33.2 75 72 73 72 115 82 82 136 2 × 5.6 6.8 7.1 2 × 6.85 13.1 13.2 2 × 10.2 2 × 13.
SELECTION PROCEDURE 1. Model Selection (With actual examples) First step, to select the approximate model: Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model.
(Step-3) Calculation of net capacity Based on the indoor conditioned temperature (WB,DB), designed outdoor temperature (DB), and the actual air flow obtained in Step-2, obtain the gross capacity from the gross capacity tables (pages 18~35). Then, calculate the net capacity from the formula below by using the fan motor input obtained in Step-2. Net capacity (kW) = Gross capacity (kW) - Fan motor input (kW) Example: PE-8MYC Condition: Indoor conditioned temp. : 26˚CDB, 19˚CWB Designed outdoor temp.
- 18 - 19.0 24 17.3 21 18.5 17.3 20 23 19.0 24 17.9 18.5 23 22 17.9 17.3 20 22 16.1 19 17.3 18.5 23 21 17.9 22 16.1 19 17.3 15.6 18 21 17.3 21 17.3 17.3 20 20 16.1 15.0 17 19 14.5 16 15.6 16.1 19 18 15.6 14.5 16 18 13.9 15 15.0 15.0 17 17 14.5 13.9 15 16 Q kW WB ˚C 7.3 8.6 9.9 11.2 12.4 4.8 6.2 7.5 8.9 10.1 12.1 3.7 4.8 6.2 7.4 9.1 10.6 3.8 5.1 6.7 8.0 9.3 11.0 3.9 5.2 6.8 8.3 10.1 4.2 5.5 7.2 SHCkW 20.0 4.
- 19 - 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.3 3.3 9.1 9.1 9.0 9.0 8.9 8.9 8.8 8.8 8.7 8.7 18 19 20 21 22 23 24 25 26 27 4.2 4.2 4.2 4.3 4.3 4.4 4.4 4.4 4.5 4.5 14.3 14.2 14.2 14.1 14.1 14.0 14.0 13.9 13.9 13.8 13.7 13.6 16 17 18 19 20 21 22 23 24 25 26 27 12.3 12.3 12.2 12.2 12.2 12.1 12.1 12.0 12.0 11.9 11.8 3.4 3.5 3.5 3.5 3.5 3.5 3.6 3.6 3.6 3.6 3.7 15.6 15.7 15.8 15.9 15.9 16.0 16.1 16.1 16.2 16.3 16.3 16.
- 20 - 5.6 5.7 5.8 0.89 0.72 0.60 0.48 13.3 11.5 9.6 7.3 18.4 19.3 19.9 21.2 22.0 17 18 19 20 21 18 19 6.3 6.5 6.1 6.3 6.4 6.5 6.8 6.3 6.4 6.5 6.6 6.9 6.4 6.5 0.49 0.25 0.80 0.66 0.50 0.41 0.22 0.89 0.70 0.59 0.48 0.28 0.84 0.74 9.4 5.3 14.9 12.8 10.3 8.7 5.1 17.2 14.2 12.4 10.5 6.7 17.2 15.6 19.3 20.4 21.2 18.7 19.3 20.4 21.2 22.1 23.0 19.3 20.4 21.2 22.1 23.0 24.0 20.4 21.2 5.9 6.1 6.2 5.8 5.9 6.1 6.2 6.3 6.4 5.9 6.1 6.2 6.3 6.4 6.6 6.1 6.2 0.
- 21 - 5.3 5.4 5.5 0.70 0.57 0.46 9.9 21.6 22.5 23.4 24.4 25.3 26.1 22.5 23.4 5.6 5.7 5.4 5.5 5.6 5.7 5.8 6.0 5.5 5.6 5.7 5.8 6.0 6.1 5.6 5.7 0.34 0.25 0.76 0.63 0.50 0.41 0.30 0.23 0.81 0.67 0.56 0.45 0.36 0.28 0.83 0.71 7.7 5.8 15.8 13.6 11.3 9.5 7.3 5.7 17.5 15.1 13.2 11.0 9.2 7.3 18.8 16.8 23.5 20.7 21.7 22.6 23.5 24.5 25.4 21.7 22.6 23.5 24.5 25.4 26.2 22.6 23.5 21 18 19 20 21 22 23 19 20 21 22 23 24 20 21 25.
- 22 - 26.1 23.5 21 18 27.9 28.8 24 26.1 21 23 25.2 20 27.0 28.8 24 22 27.9 25.2 20 23 24.4 19 27.0 27.9 23 22 27.0 22 26.1 26.1 21 21 25.2 20 24.4 25.2 20 19 24.4 22.7 17 19 22.0 16 23.5 24.4 19 18 23.5 22.0 16 18 21.3 15 22.7 22.7 17 17 22.0 21.3 15 16 Q kW WB ˚C 11.9 13.8 16.1 18.5 21.0 7.9 10.0 11.9 14.4 16.6 19.2 6.0 8.0 10.4 12.3 14.7 17.4 6.1 8.1 10.7 12.9 15.1 18.1 6.2 8.7 11.1 13.8 16.2 6.6 9.0 11.
- 23 - 5.9 6.0 5.8 5.9 6.0 6.1 6.2 5.9 0.41 0.29 0.77 0.62 0.48 0.36 0.26 0.82 9.4 6.9 17.0 14.1 11.4 8.9 6.6 18.8 22.9 23.8 22.0 22.9 23.8 24.7 25.6 22.9 16 17 15 16 17 18 19 16 17 6.1 6.2 6.3 6.4 6.1 0.55 0.44 0.33 0.24 0.73 13.5 11.2 8.6 6.5 18.1 24.7 25.6 26.5 27.4 24.7 19 20 21 18 30.8 29.0 28.2 27.3 26.4 30.8 29.0 28.2 27.3 26.4 25.5 29.0 28.2 27.3 26.4 25.5 24.6 27.3 26.4 25.5 24.6 23.8 22.9 25.5 24.6 23.8 22.
- 24 - 26.1 23.5 21 18 27.9 28.8 24 26.1 21 23 25.2 20 27.0 28.8 24 22 27.9 25.2 20 23 24.4 19 27.0 27.9 23 22 27.0 22 26.1 26.1 21 21 25.2 20 24.4 25.2 20 19 24.4 22.7 17 19 22.0 16 23.5 24.4 19 18 23.5 22.0 16 18 21.3 15 22.7 22.7 17 17 22.0 21.3 15 16 Q kW WB ˚C 11.9 13.8 16.1 18.5 21.0 7.9 10.0 11.9 14.4 16.6 19.2 6.0 8.0 10.4 12.3 14.7 17.4 6.1 8.1 10.7 12.9 15.1 18.1 6.2 8.7 11.1 13.8 16.2 6.6 9.0 11.
- 25 - 5.9 6.0 5.8 5.9 6.0 6.1 6.2 5.9 0.41 0.29 0.77 0.62 0.48 0.36 0.26 0.82 9.4 6.9 17.0 14.1 11.4 8.9 6.6 18.8 22.9 23.8 22.0 22.9 23.8 24.7 25.6 22.9 16 17 15 16 17 18 19 16 17 6.1 6.2 6.3 6.4 6.1 0.55 0.44 0.33 0.24 0.73 13.5 11.2 8.6 6.5 18.1 24.7 25.6 26.5 27.4 24.7 19 20 21 18 30.8 29.0 28.2 27.3 26.4 30.8 29.0 28.2 27.3 26.4 25.5 29.0 28.2 27.3 26.4 25.5 24.6 27.3 26.4 25.5 24.6 23.8 22.9 25.5 24.6 23.8 22.
- 26 9.1 0.70 23.6 33.6 COOLING CAPACITY TOTAL INPUT SHC AIR VOLUME 80 1,330 0.977 0.991 0.968 CMM L/S Factor for Various Air Flow PE-10MYC-EU PEH-10MYA-EU 0.41 1,550 1.0 1.0 1.0 90 SHC:SENSIBLE HEAT CAPACITY 15.1 14.8 0.41 10.0 9.9 0.50 17.3 34.6 35.7 9.8 0.60 9.6 0.72 23.2 32.4 20.1 9.5 0.80 26.0 32.4 33.5 10.0 9.9 9.8 9.6 9.5 9.4 9.9 9.8 9.6 9.5 9.4 9.3 9.6 9.5 9.4 9.3 9.2 9.2 9.4 9.3 9.2 9.2 9.1 9.2 9.2 9.1 T/I kW 0.28 0.36 0.46 0.58 0.
- 27 - 0.39 0.28 0.74 0.59 0.46 0.35 0.25 0.79 0.63 0.52 0.42 0.31 0.22 0.69 12.3 9.1 22.0 18.4 14.8 11.7 8.8 24.4 20.6 17.6 14.7 11.3 8.6 23.5 31.1 32.5 29.7 31.1 32.5 33.9 35.3 31.1 32.5 33.9 35.3 36.7 38.1 33.9 16 17 15 16 17 18 19 16 17 18 19 20 21 18 0.45 0.39 18.5 16.0 40.9 40.5 24 0.66 25.0 38.1 21 23 0.76 28.0 36.7 20 0.55 0.27 10.8 40.5 24 21.9 0.33 13.6 40.9 23 39.5 0.41 16.3 39.5 22 22 0.52 20 0.61 0.
- 28 9.1 0.70 23.6 33.6 COOLING CAPACITY TOTAL INPUT SHC AIR VOLUME 80 1,330 0.977 0.991 0.968 CMM L/S Factor for Various Air Flow PE-10MYC-EU PEH-10MYA-EU 0.41 1,550 1.0 1.0 1.0 90 SHC:SENSIBLE HEAT CAPACITY 15.1 14.8 0.41 10.0 9.9 0.50 17.3 34.6 35.7 9.8 0.60 9.6 0.72 23.2 32.4 20.1 9.5 0.80 26.0 32.4 33.5 10.0 9.9 9.8 9.6 9.5 9.4 9.9 9.8 9.6 9.5 9.4 9.3 9.6 9.5 9.4 9.3 9.2 9.2 9.4 9.3 9.2 9.2 9.1 9.2 9.2 9.1 T/I kW 0.28 0.36 0.46 0.58 0.
- 29 - 0.39 0.28 0.74 0.59 0.46 0.35 0.25 0.79 0.63 0.52 0.42 0.31 0.22 0.69 12.3 9.1 22.0 18.4 14.8 11.7 8.8 24.4 20.6 17.6 14.7 11.3 8.6 23.5 31.1 32.5 29.7 31.1 32.5 33.9 35.3 31.1 32.5 33.9 35.3 36.7 38.1 33.9 16 17 15 16 17 18 19 16 17 18 19 20 21 18 0.45 0.39 18.5 16.0 40.9 40.5 24 0.66 25.0 38.1 21 23 0.76 28.0 36.7 20 0.55 0.27 10.8 40.5 24 21.9 0.33 13.6 40.9 23 39.5 0.41 16.3 39.5 22 22 0.52 20 0.61 0.
- 30 - 25.1 19.5 14.3 39.7 33.5 28.8 23.7 18.4 14.0 38.0 47.0 48.5 50.2 52.1 47.0 48.5 50.2 52.1 53.8 55.8 50.2 16 17 18 19 16 17 18 19 20 21 18 32.8 27.5 23.5 17.9 14.1 42.3 36.3 31.8 26.8 22.4 18.0 45.7 40.8 35.4 30.6 26.8 53.8 55.8 57.7 59.6 52.1 53.8 55.8 57.7 59.6 61.5 53.8 55.8 57.7 59.6 61.5 20 21 22 23 19 20 21 22 23 24 20 21 22 23 24 35.8 52.1 19 30.3 45.5 15 15.2 48.5 17 20.4 26.1 47.0 45.
- 31 - 52.2 47.0 21 18 55.8 57.6 24 52.2 21 23 50.4 20 54.0 57.6 24 22 55.8 50.4 20 23 48.8 19 54.0 55.8 23 22 54.0 22 52.2 52.2 21 21 50.4 20 48.8 50.4 20 19 48.8 45.4 17 19 44.0 16 47.0 48.8 19 18 47.0 44.0 16 18 42.6 15 45.4 45.4 17 17 44.0 42.6 15 16 Q kW WB ˚C 15.6 0.44 25.1 16.1 16.3 0.52 0.44 28.1 24.9 54.2 56.0 COOLING PEH-15MYA-EU CAPACITY TOTAL INPUT SHC AIR VOLUME 120 2,000 0.976 0.991 0.
- 32 - 54.8 49.4 21 18 0.24 0.81 0.67 0.57 0.46 0.37 0.28 0.83 0.72 13.8 41.4 35.6 31.3 26.1 21.8 17.5 44.2 39.6 56.6 58.4 51.2 53.0 54.8 56.6 58.4 62.6 53.0 54.8 23 19 20 21 22 23 24 20 21 0.61 0.51 0.41 34.7 29.6 25.6 56.6 58.4 62.6 23 24 0.31 22 17.5 0.41 22 22.7 54.8 0.50 21 26.7 0.63 0.76 0.26 0.35 0.46 0.57 0.69 0.85 0.28 0.38 0.50 0.64 0.80 0.31 0.43 0.57 53.0 32.2 37.3 14.1 18.4 23.5 28.1 32.7 38.8 14.4 19.
- 33 - 73.8 71.8 69.4 67.2 67.2 73.8 71.8 69.4 67.2 67.2 62.4 71.8 69.4 67.2 67.2 62.4 60.4 67.2 67.2 62.4 60.4 58.2 56.2 62.4 60.4 58.2 56.2 54.0 58.2 56.2 54.0 Q kW COOLING CAPACITY TOTAL INPUT SHC AIR VOLUME 160 2,660 0.976 0.991 0.963 CMM L/S Factor for Various Air Flow PE-20MYC-EU 30.4 35.4 41.4 47.9 53.5 20.5 26.4 31.3 38.3 43.2 50.1 16.2 20.8 27.4 32.5 39.3 45.3 15.9 21.2 27.9 33.6 39.0 47.1 17.1 22.8 28.9 35.7 42.3 17.6 23.6 30.
- 34 - 60.0 17 58.2 17.9 19.0 0.75 45.3 60.4 17.9 0.74 46.0 62.2 18 19.2 19.4 19.7 19.9 20.1 20.3 19.4 19.7 0.64 0.57 0.45 0.37 0.28 0.80 0.71 43.2 38.3 31.3 20.5 53.5 47.9 67.2 67.2 69.4 71.8 73.8 67.2 67.2 18.1 18.4 18.6 18.8 19.0 19.2 18.4 18.6 0.63 0.56 0.45 0.36 0.28 0.79 0.71 43.9 38.8 31.9 26.8 21.0 54.5 48.8 69.2 69.2 71.6 73.8 76.0 69.2 69.2 21 22 23 24 20 21 19.0 19.2 0.49 0.41 36.2 31.1 73.8 76.0 23 24 20.1 20.3 0.49 0.41 35.
- 35 - 17.2 17.4 17.6 17.6 17.8 17.2 17.4 0.62 0.52 0.42 0.34 0.27 0.77 0.66 45.3 39.8 33.1 27.6 22.1 56.4 50.5 73.4 76.2 79.0 81.8 82.0 73.4 76.2 20 21 22 23 24 20 21 81.2 81.6 78.8 76.0 73.2 81.2 81.6 78.8 76.0 73.2 70.4 81.6 78.8 76.0 73.2 70.4 67.6 76.0 73.2 70.4 67.6 64.8 62.0 70.4 67.6 64.8 62.0 59.2 64.8 62.0 59.2 32.2 37.4 44.0 50.3 56.2 21.9 27.5 33.0 39.7 45.2 52.5 17.2 22.0 28.6 33.8 40.8 47.4 17.5 23.0 29.
CAPACITY REDUCTION RATIO DUE TO CHANGES IN PIPING LENGTH (1) Cooling capacity PE-7,8,15MYC-EU PEH-7,8,15MYA-EU Capacity ratio 1.0 0.9 0 5 10 15 20 25 30 35 40 45 50 40 45 50 Equivalent piping length (m) PE-10,20MYC-EU PEH-10,20MYA-EU Capacity ratio 1.0 0.9 0 5 10 15 20 25 30 35 Equivalent piping length (m) (2) Heating capacity Model name Equivalent piping length PEH-7, 8, 10, 15, 20MYA - 36 - ~30m 30~50m 1.0 0.
OPERATION RANGE The range of working temperatures is as below. Make sure which unit you are using and confirm the range of application. Cooling Heating (PEH only) 40 30 Range for continuous operation 20 10 0 -5 -10 10 15 20 24 25 30 Indoor temp.(˚CWB) Range for continuous operation Use for low ambient cooling parts (without PU-15,20) Outdoor temp.(˚CWB) Outdoor temp.
FAN PERFORMANCE PE-7MYC-EU PEH-7MYA-EU PEH-5MYA-EU Fan Performance Curve 50Hz (Pa) 450 450 Recommended Range 400 400 Fan speed (rpm) 350 Recommended Range Fan speed (rpm) 1400 350 1300 1300 300 1200 Total static pressure Total static pressure Fan Performance Curve 50Hz (Pa) For connection operation line 250 1100 200 1000 150 900 For connection operation line For Hi speed operation line 300 1200 250 200 150 1100 For Low speed operation line 1000 900 800 100 Inte r 100 SP nal Inte
PE-15MYC1-EU PEH-15MYA-EU Total static pressure (Pa) 200 Fan Performance Curve 50Hz Recommended Range (Pa) 1000 300 Fan speed (rpm) 1300 Total static pressure 800 600 3.
Pulley outside dimensions are shown below: (Unit : mm) (1) Shape of belt groove e f K0 Shape of V-belt Nominal Dia. øP.C B Over 125 Under 160 Over 160 Under 200 Over 200 a (˚) W 34 15.86 36 16.07 38 16.29 øP.C r3 r1 a r2 r2 K w L0 L0 K K0 e f r1 r2 r3 V-belt thickness (Reference) 12.5 5.5 9.5 19.0 12.5 0.2~0.5 0.5~1.0 1~2 11 Sectional plan of V-belt 11.0mm 16.5mm 40˚ B type (2) Shape of motor pulley boss (Unit : mm) C B A MOTOR CAPACITY (kW) A +0.028 2.2, 3.
SOUND DATA Indoor units Sound Levels MODEL PEH-5MYA-EU PE-7MYC-EU PEH-7MYA-EU PE-8MYC-EU PEH-8MYA-EU PE-10MYC-EU PEH-10MYA-EU PE-15MYC1-EU PEH-15MYA-EU PE-20MYC-EU PEH-20MYA-EU OCTAVE BAND FREQ. Hz SPL dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz 55 60.5 57.5 57.5 52.5 50.5 43 34.5 28.5 55 62 60 54 53 50 42.5 37 31.5 56 63 61 55 54 51 43.5 38 32.5 59 62 62.5 58.5 59.5 53 48 43.5 36 61 25 40 47 52 55 57.5 52 36.5 62 32 44 49 53.5 56.
APPROXIMATION FOR SOUND POWER LEVEL AT SUPPLY DUCT FLANGE OF UNIT Air volume 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz External static pressure PE(H)-7 60 125 77.2 74.7 71.6 69.9 65.7 61.4 PE(H)-8 70 125 79.4 76.9 73.9 72.4 68.4 64.3 PE(H)-10 90 125 81.2 78.7 75.7 74.3 70.4 66.5 PE(H)-15 140 200 83.4 80.9 78.0 76.6 72.7 68.9 PE(H)-20 180 200 84.5 82.1 79.1 77.7 73.8 70.
OUTLINE DIMENSIONS (unit; mm) PEH-5 POWER SUPPLY CABLE ENTRY ø27 (Bottom side) 104 130 130 130 130 130 66 HOLES:18-ø3.1 AIR INLET DUCT FLANGE 40 55 50 105 960 20 200 40 199 40 OPTIONAL PARTS CABLE ENTRY ø27 (Bottom side) 34 782 135 66 CONTROL CABLE ENTRY ø27 (Bottom side) *Except: Drain size (unit; inch) 20 131 CONTROL BOX 55 AIR OUTLET DUCT FLANGE 130 130 130 55 15 HOLES:14-ø3.1 HOLES:4-ø12 1095 650 50 40 920 15 210 210 98 250 428 REFRIGERANT PIPE ø12.
PE(H)-10 104 POWER SUPPLY CABLE ENTRY 27 (Bottom side) 1302 66 130 135 130 130 130 34 130 130 130 130 HOLES:26- 3.1 130 66 CONTROL 105 40 (Bottom side) 1480 20 20 200 40 (Bottom side) 199 40 OPTIONAL PARTS CABLE ENTRY 27 AIR INLET DUCT FLANGE 50 27 55 CABLE ENTRY HOLES:22- 3.1 45 130 130 130 AIR OUTLET DUCT FLANGE HOLES:4- 12 25 AIR OUTLET 40 98 220 REFRIGERANT PIPE 15.88 (5/8) Braze 250 382 100 100 280 45 1440 1000 220 REFRIGERANT PIPE 28.
PE(H)-20 70 1993 1648 193 44 49 1560=130X12 AIR INLET DUCT FLANGE 63 50 POWER SUPPLY CABLE ENTRY 27 (BOTTOM SIDE) 3.1 15 HOLES:38- 44 130 620 40 12 63 HOLES:4- 130 21 1170=130X9 536 81 25 1940 25 CABLE ENTRY 27 REFRIGERANT CONTROL BOX PIPE 15.88 (5/8) Braze REFRIGERANT PIPE 28.6 (1-1/8) Braze AIR OUTLET DUCT FLANGE 15 190 44 40 REFRIGERANT PIPE 15.88 (5/8) Braze REFRIGERANT PIPE 28.
PUH-5 75 AIR INLET 400 AIR INLET 75 Holes :4-12 × 20 21 1040 550 AIR OUTLET 21 1000 1175 SERVICE PANEL 131 126 REFRIGERANT PIPE ø12.7 (1/2) Flare CABLE ENTRY 21 Hole : ø15 Holes : 2-ø15 75 18 PU(H)-7,8,10 (Upper blow) AIR INLET 275 275 13 400 42 75 42 84 75 REFRIGERANT PIPE ø19.05 (3/4) Flare 200 CABLE ENTRY 25X40 1000 350 13 724 AIR INLET 700 AIR OUTLET Holes: 4-12 × 20 SERVICE PANEL 120 980 AIR INLET 34 28 100 235 175 REFRIGERANT PIPE PU(H)- 7,8:ø25.
PUH-8,10 (Side blow) 400 75 AIR INLET Holes : 4-12 × 20 75 AIR INLET 21 1290 21 AIR OUTLET 550 1250 1175 SERVICE PANEL REFRIGERANT PIPE ø15.88(5/8) Flare 130 CABLE ENTRY REFRIGERANT PIPE PUH-8:ø25.4(1) Flange PUH-10:ø28.6(1-1/8) Flange 44 49 Hole : ø15 400 75 56 42 75 42 84 75 Holes : 2-ø15 275 275 ACCESSORY PIPE PU-15 23 AIR INLET 23 1046 AIR INLET AIR INLET AIR OUTLET 998 998 HOLES: 4-Uø15 SERVICE PANEL 1070 REFRIGERANT PIPE ø25.
PU-20 464 35 AIR INLET AIR INLET 464 AIR INLET No.1 17 35 30 52 48 HOLES: 6-ø15 No.2 2036 17 ACCESSORY PIPE REFRIGERANT PIPE ø15.88(5/8) Flare REFRIGERANT PIPE ø28.6(1-1/8) Flange 1996 160 SERVICE PANEL CONTROL CABLE ENTRY ø27 801 POWER SUPPLY CABLE ENTRY ø47 392 81 85 213 80 961 AIR OUTLET 998 756475 750 130 PUH-15,20 200 Holes : 4-12 × 20 27 830 2005 478.5 27 994 CONTROL BOX REFRIGERANT PIPE ø15.88 (5/8) Flare 1042 1200 SERVICE PANEL REFRIGERANT PIPE PUH-15:ø25.
Note: In the case of installation are shown below, it is possible to use the unit by connecting the duct. However, the pressure loss must be 30Pa (3mmAq) or less. Duct work is local supply.
WIRING DIAGRAMS PE-7MYC-EU /PU-7MYC1-EU (STANDARD) OUTDOOR TB1 L2 RED F3(3.
PE-8,10MYC-EU/PU-8,10MYC1-EU (STANDARD) TB1 OUTDOOR RED L1 L2 POWER SUPPLY 380~415VAC 3N~PE 50Hz RED L3 N 52C WHITE BLACK BLACK F3(3.
PE-15MYC1-EU/PU-15MYC1-EU (STANDARD) TB1 OUTDOOR L2 L3 CIRCUIT BREAKER (FIELD SUPPLY) PU-15MYC1-EU···100A N 52C1 RED L1 POWER SUPPLY 380~415VAC 3N~PE 50Hz RED WHITE WHITE 52C2 RED 51C2 RED 52F2 RED 51F2 WHITE BLACK BLACK BLACK MC2 L1 RED 51 F2 18 52 C1 52 C2 VIOLET 49C1 19 VIOLET ORANGE C14 17 16 ORANGE C24 1 CH1 2 20 1 1 CH2 25 51C1 23 26 VIOLET 21 30 CZ2-1 CZ1 3 3 22 TB5 N N WHITE BLUE 51F1 MF1 BLACK F1 (3.15A) RED PE L1 F2 (3.
PE-20MYC-EU/PU-20MYC1-EU (STANDARD) OUTDOOR TB1 L2 L3 N RED 51C1 52C1 RED L1 POWER SUPPLY 380~415VAC 3N~PE 50Hz WHITE 51C2 52C2 RED PE CIRCUIT BREAKER (FIELD SUPPLY) PU-20MYC1-EU···125A WHITE BLACK BLACK F3 (3.15A) 52F2 L1 RED 24 52 C2 19 25 17 C14 C24 20 1 21 3 2 26 51C1 CR2 30 CZ1 52 VIOLET C1 22 30 CZ1 2 52 ORANGE C2 RED L2 L3 WHITE 52 F2 2 N GRAY 13 BLUE 51F1 L1 F2 (3.
PE-7MYC-EU / PU-7MYC1-EU (SPECIAL ORDER : LOW AMBIENT COOLING) OUTDOOR TB1 L2 RED F3(3.
PE-8,10MYC-EU / PU-8,10MYC1-EU (SPECIAL ORDER : LOW AMBIENT COOLING) TB1 OUTDOOR RED L1 L2 POWER SUPPLY 380~415VAC 3N~PE 50Hz RED L3 N 52C WHITE BLACK BLACK F3(3.15A) L1 BLUE 51F2 CIRCUIT BREAKER (FIELD SUPPLY) WHITE 2 BLACK 3 52C L1 U LOW AMBIENT COOLING PARTS L2 V L3 W TH TB5 18 16 VIOLET C14 15 1 19 C13 22 VIOLET CZ2 30 CZ 3 21 TB6 30 CZ 51F1 52F RED L2 L3 WHITE C01RED 1 2 3 BLACK RED WHITE BLACK BLUE TB2 L1 RED 14 CR2 F1 (3.
PEH-5MYA-EU/PUH-5MYE1-EU (STANDARD) TB1 OUTDOOR L2 POWER SUPPLY 380~415VAC 3N~PE 50Hz RED 51C RED WHITE WHITE BLACK L1 RED CIRCUIT BREAKER (FIELD SUPPLY) PUH-5MYE1-EU···50A (*1) HZ2 51F2 17 22 FC TB6 VIOLET C14 52C 1C11RED 2 WHITE MF2 3 BLACK X1 WHITE F3(3.
PEH-7MYA-EU/ PUH-7MYC2-EU (STANDARD) OUTDOOR TB1 L2 RED F3(3.
PEH-8,10MYA-EU/PUH-8,10MYC2-EU (STANDARD) PEH-8,10MYA-EU/PUH-8,10MYE1-EU OUTDOOR L1 TB1 L2 POWER SUPPLY 380~415VAC 3N~PE 50Hz N 51C RED WHITE WHITE BLUE PE 1C11RED 2 WHITE MF2 3 BLACK X1 BLACK L1 RED (*1) 1C21 RED 2 WHITE MF3 3 BLACK HZ2 51F2 23 17 VIOLET BROWN FC TB6 (*1) 49C 52C 18 X1 X2 C14 16 51F2 RED WHITE F3(3.
PEH-15,20MYA-EU/PUH-15,20MYC2-EU (STANDARD) OUTDOOR L1 TB1 WHITE BLACK BLACK BLUE N WHITE BLACK 52C2 WHITE F3(3.
PEH-7MYA-EU / PUH-7MYC2-EU (SPECIAL ORDER : LOW AMBIENT COOLING) OUTDOOR TB1 L2 RED F3(3.
PEH-8,10MYA-EU / PUH-8,10MYE1-EU PEH-8,10MYA-EU / PUH-8,10MYC2-EU (SPECIAL ORDER : LOW AMBIENT COOLING) TB1 BLUE RED WHITE F3(3.15A) PE PUH- 8MYC2-EU···50A PUH-10MYC2-EU···60A PUH- 8MYE1-EU···50A PUH-10MYE1-EU···60A FC N X1 24 51C C15 CR2 VIOLET 52C 21 S4 T1 X2 3 N BLUE TB2 RED F1 (3.15A) C01 RED X WHITE U WHITE V Y BLUE MF1 Z RED BLUE W C02 TB4 1 GRAY F2 (3.
PEH-15,20MYA-EU / PUH-15,20MYC2-EU (SPECIAL ORDER : LOW AMBIENT COOLING) OUTDOOR L1 TB1 WHITE BLACK BLACK BLUE N WHITE BLACK 52C2 RED L1 HZ2 52C2 C14 VIOLET ORANGE 19 C23 C13 1 1 CH1 23 24 VIOLET C24 1 2 25 22 VIOLET 20 TB2 28 30 CZ2 ORANGE 2 CZ 2-2 52 T2 C28 TH1 41 3 N L3 W GRAY GRAY 11 12 13 CZ 2-1 CZ 2-2 TH2 FC N HZ2 GRAY PINK 14 T4 X2 BLUE N 51F1 52F WHITE MF1 BLACK L1 GRAY RED NOTE 4 C03 C03 RED 1 SILVER 51F1 F2 (3.
ELECTRICAL OPERATION FLOW CHARTS PE-7,8,10MYC-EU PEH-5MYA-EU, PEH-7,8,10MYA-EU START START POWER ON POWER ON CH ON CH ON 30FZ,30CZ ON (SELF HOLD) 30FZ,30CZ ON (SELF HOLD) LCD controller ON? NO YES YES FZ ON FZ ON 52F ON MF1 OPERATE LCD controller COMP ON? 52F ON MF1 OPERATE NO YES CZ1,2 NO LCD controller ON? NO COOL MODE? HZ1,2 ON 21S4 YES ON NO LCD controller COMP ON? 52C ON MC OPERATE MF2, 3 OPERATE NO YES CZ1 LCD controller COMP ON? ON YES CZ1,2 CH OFF SAFETY DEVICE O
PE-15MYC1-EU PE-20MYC-EU START START POWER ON POWER ON CH1,2 ON CH1,2 ON 30FZ,30CZ1,2 ON (SELF HOLD) 30FZ,30CZ1,2 ON (SELF HOLD) NO LCD controller ON? YES YES FZ ON FZ ON 52F1 ON MF1 OPERATE 52F1 ON MF1 OPERATE NO LCD controller COMP ON? NO LCD controller COMP ON? YES YES CZ1-1,CZ2-1 ON CZ1-1,CZ2-1 ON 52C1 ON MC1 OPERATE MF2 OPERATE 52C1 ON MC1 OPERATE MF2 OPERATE CH 1 OFF CH 1 CZ1-2,CZ2-2 ON TIMER 2 ON NO PASS THE 3 MIN? 52C2 ON MC2 OPERATE CH2 OFF CH2 No.
PEH-15,20MYA-EU START POWER ON CH1,2 ON 30FZ,30CZ1,2 ON (SELF HOLD) NO LCD controller ON? YES FZ ON 52F1 ON MF1 OPERATE NO COOL MODE? HZ1,2 ON 21S4-1,2 ON T1,T2 ON YES NO LCD controller COMP ON? YES YES CZ1-1,CZ2-1 ON CZ1-1,CZ2-1 ON 52C1 MC1 MF2 52C1 MC1 MF2 CH 1 ON OPERATE OPERATE CH 1 OFF NO PASS THE 3 MIN? OFF PASS THE 3 MIN? YES CH 2 ON OPERATE OPERATE CZ1-2,CZ2-2 ON TIMER 2 ON CZ1-2,CZ2-2 ON TIMER 2 ON 52C2 MC2 MF3 NO LCD controller COMP ON? NO PASS THE 30 MIN ON? (T1) YE
REFRIGERANT SCHEMATICS PE-7,8,10,20MYC-EU PE-15MYC1-EU INDOOR PE Evaporator BRAZING FRANGE FLARE OUTDOOR PU Condenser High pressure switch Service port Check joint Strainer Ball valve COOL Muffler Accumulator Check joint Compressor Capillary Tube Strainer Ball valve Note: PE-15MYC1,20MYC-EU is comprised of two refrigerant cycles.
SAFETY & CONTROL DEVICES PE-7,8,10MYC-EU PE-15MYC1-EU PE-20MYC-EU NO. PE-7MYC-EU PU-7MYC1-EU PE-8MYC-EU PU-8MYC1-EU PE-10MYC-EU PU-10MYC1-EU COMPRESSOR OVER CURRENT RELAY 51C 19.0A 22.0A 31.0A COMPRESSOR INTERNAL THERMOSTAT 49C 105 ± 5 ˚C OF83 ± 11 ˚C ON HIGH PRESSURE SWITCH 63H 2.94MPa OFF INDOOR FAN MOTOR OVER CURRENT RELAY 51F1 INDOOR FAN MOTOR INTERNAL THERMOSTAT - 150 ˚C OFF OUTDOOR FAN MOTOR OVER CURRENT RELAY 51F2 2.
PEH-7,8,10MYA-EU PEH-15,20MYA-EU ITEM NO. PEH-8MYA-EU PUH-8MYC2-EU PUH-8MYE1-EU PEH-5MYA-EU PEH-7MYA-EU PUH-5MYE1-EU PUH-7MYC2-EU COMPRESSOR OVER CURRENT RELAY 51C 15.0A 19.0A COMPRESSOR INTERNAL THERMOSTAT 49C 110 ± 5˚C OFF 61 ± 9˚C ON 22.0A 105 ± 5˚C OFF 83 ± 11˚C ON HIGH PRESSURE SWITCH 63H1 2.94MPa OFF HIGH PRESSURE SWITCH (DEFROST) 63H2 2.16MPa OFF 26D -4 ± 1.5 ˚C ON,26± 1.
SPECIAL ORDER Description Model PEH-5MYA PEH-7MYA PEH-8MYA PEH-10MYA PEH-15MYA PEH-20MYA Service ref.
PHYSICAL DATA PE-7,8,10,20MYC-EU PE-15MYC1-EU [ PRODUCT] Product type Product number : PACKAGE AIR COOLED HEATPUMP UNITS Indoor unit Outdoor unit Cooling capacity (AS1861) Sensible Cooling capacity (AS1861) Cooling power consumption (Input) Basic temperature condition cooling Basic temperature condition cooling PE-7MYC-EU PU-7MYC1-EU 17.9 14.3 7.2 kW kW kW Indoor Outdoor PE SERIES PE-8MYC-EU PE-10MYC-EU PE-15MYC1-EU PE-20MYC-EU PU-8MYC1-EU PU-10MYC1-EU PU-15MYC1-EU PU-20MYC1-EU 57.6 47.0 22.0 28.8 46.
Product number Indoor unit PE-7MYC-EU PU-7MYC1-EU Outdoor unit PE-8MYC-EU PU-8MYC1-EU PE-10MYC-EU PE-15MYC1-EU PE-20MYC-EU PU-10MYC1-EU PU-15MYC1-EU PU-20MYC1-EU [INDOOR AIR CIRCUIT] Number of blowers Diameter of blowers Width of blowers Blower drive Fan motor output Fan motor run current Air quantity External static pressure Supply air dimensions(hxw) Return air dimensions(hxw) [EVAPORATOR] Number of evaporator Face area Rows deep Rows high Finned length Face velocity Fin per meter Fin material thic
Product number Indoor unit Outdoor unit PE-7MYC-EU PU-7MYC1-EU PE-8MYC-EU PU-8MYC1-EU PE-10MYC-EU PE-15MYC1-EU PE-20MYC-EU PU-10MYC1-EU PU-15MYC1-EU PU-20MYC1-EU [ENCLOSURE AND FRAME] Dimension Dimension Indoor unit Outdoor unit External finish (indoor unit) (outdoor unit) External finish Panel thickness Condense drain size Wei ght Indoor unit Wei ght Outdoor unit Sound pressure level (indoor unit) Sound pressure level (outdoor unit) Sound power level (indoor unit) Sound power level (outdoor unit)
PEH-5,7,8MYA-EU [ PRODUCT] Product type Product number : PACKAGE AIR COOLED HEATPUMP UNITS Indoor unit Outdoor unit Cooling capacity (AS1861) Sensible Cooling capacity (AS1861) Cooling power consumption (Input) Heating capacity (AS1861) Heating power consumption Basic temperature condition cooling Basic temperature condition cooling Basic temperature condition heating Basic temperature condition heating kW kW kW kW kW PEH-5MYA-EU PUH-5MYE1-EU 14.4 11.5 5.5 14.4 4.
Product number Indoor unit Outdoor unit PEH-5MYA-EU PUH-5MYE1-EU PEH-7MYA-EU PUH-7MYC2-EU PEH-8MYA-EU PUH-8MYC2-EU PUH-8MYE1-EU [INDOOR AIR CIRCUIT] Number of blowers Diameter of blowers Width of blowers Blower drive Fan motor output Fan motor run current Nominal air quantity External static pressure Supply air dimensions(hxw) Return air dimensions(hxw) [EVAPORATOR] Number of evaporator Face area Rows deep Rows high Finned length Face velocity Fin per meter / pitch Fin material thickness Fin material/
Product number Indoor unit Outdoor unit PEH-5MYA-EU PUH-5MYE1-EU PEH-7MYA-EU PUH-7MYC2-EU PE-8MYA-EU PUH-8MYC2-EU PUH-8MYE1-EU [ENCLOSURE AND FRAME] Dimension Indoor unit Dimension Outdoor unit External finish (indoor unit) (outdoor unit) External finish Panel thickness Condense drain size Weight Indoor unit Weight Outdoor unit Sound pressure level (indoor unit ) Sound pressure level (outdoor unit ) Sound power level (indoor unit ) Sound power level (outdoor unit ) width depth height width depth
PEH-10,15,20MYA-EU [ PRODUCT] Product type Product number : PACKAGE AIR COOLED HEATPUMP UNITS PEH SERIES PEH-15MYA-EU PEH-10MYA-EU PUH-15MYC2-EU PUH-10MYC2-EU PUH-10MYE1-EU 44.0 28.8 35.2 23.0 10.1 10.2 16.9 28.8 44.0 8.3 14.
Product number Indoor unit Outdoor unit PEH-15MYA-EU PUH-15MYC2-EU PEH-10MYA-EU PUH-10MYC2-EU PUH-10MYE1-EU PEH-20MYA-EU PUH-20MYC2-EU [INDOOR AIR CIRCUIT] Number of blowers Diameter of blowers Width of blowers Blower drive Fan motor output Fan motor run current Nominal air quantity External static pressure Suppl y air dimensions(hxw) Return air dimensions(hxw) [EVAPORATOR] Number of evaporator Face area Rows deep Rows hi gh Finned length Face velocit y Fin per meter / pitch Fin material thickness Fin
Product number Indoor unit Outdoor unit PEH-10MYA-EU PUH-10MYC2-EU PUH-10MYE1-EU PEH-15MYA-EU PUH-15MYC2-EU 1615 650 428 1690 PEH-20MYA-EU PUH-20MYC2-EU [ENCLOSURE AND FRAME] Dimension Indoor unit Dimension Outdoor unit External finish (indoor unit) (outdoor unit) External finish Panel thickness Condense drain size Weight Indoor unit Weight Outdoor unit Sound pressure level (indoor unit ) Sound pressure level (outdoor unit ) Sound power level (indoor unit ) Sound power level (outdoor unit ) wid
INSTALLATION 1. Space required around unit Indoor unit Dimension of the unit and space necessary for sevicing.
PU(H)-7,8, 10 (Upper blow) (1) At a single installation 300 over The obstacle is on the outlet side. (Fig 1) The obstacle is in three directions. (Fig 2,3) The obstacle is in four directions. (Fig 4) ceiling 1200 over The right and left side and the back and forth side must be opened. 300 over 500 over However, the outlet side must be opened. Service Panel Fig 2 Fig 1 300 over A If this side is service panel, you need 500 over. If this side is inlet, you need 300 over.
PU-15 (1) At a single installation The obstacle is on the outlet side. (Fig 1) The obstacle is in four directions. (Fig 2) 300 over ceiling However, the outlet 500 over side must be opened. 1500 over The right and left side and the back and forth side must be opened. 300 over 300 over Service Panel Fig 1 Fig 2 300over (2) Relation of unit when many set up unit. (Fig 3,4) 500over Service-panel 500 over 300 over If this side is service panel, you need 500 over.
PUH-15, 20 (1) At a single installation The obstacle is on the outlet side. (Fig 1) The obstacle is in four directions. (Fig 2) The obstacle is in three directions. (Fig 3,4) ceiling 1500 over 500 over The right and left side and the back and forth side must be opened. 300 over 300 over However, outlet side must be opened. And the obstacle in two directions must be lower than the unit. Service Panel Fig 2 Fig 1 However, the outlet side must be opened.
3. Installation of the unit. Indoor unit Please carry the packed until parallelly to installed place. Please install the unit before construction of the ceiling -lined. PEH-5 PE(H)- 7, 8, 10 100 over 100 over U washer Nut 30 30 Washer Nut 100 over PE(H)-15, 20 Nut (M10) Nut (M10) Washer 30 Washer Nut (M10) Ceiling Nut (M10) Outdoor unit Fix unit tightly with bolts as shown below so that unit will be securely fixed in place use concrete or angle foundation of unit.
Duct construction Provide canvas flexible ducting between unit when connect to the duct-work. The duct unit must use a nonflammable material. Provide sufficient insulation for prevent dewdrop. Duct earth Duct earth Canvas Duct Canvas Duct Duct Duct Drain pan Inlet Outlet Duct-work length 850mm or more Lifting method When the unit is to be lifted and moved, attach ropes to the suspension plates(3 p.c.s) provided on the top of the unit.
Piping connection Warning Please follow the following procedures, during the piping connection work is carried out. If the procedures are not followed properly, the refrigerant and valve sheet might gush out from the ball valve. It might cause the injury. 1. PROCEDURE TO CONNECT THE EXTENSION PIPE Proceed with the connection as follows. (1) Open the ball valve cap at first. (Fig. 1) (2) Check the ball valve section is completely closed. (Fig. 2) Valve knob Fig. 1 Valve knob Close Open Pin Pin Fig.
4. Refrigerant piping Extension piping and installation parts are field supply. C Perform the work only after carefully reading the appropriate instructions. A Install the unit where the refrigerant piping is shortest, When the outdoor unit is lower the difference between the indoor unit and outdoor unit is smallest. As pipes purchased in the market may contain dust, below them off with dry inlet gas. C Take care not to allow dust and water content to enter the piping during pipe processing or installing.
Airtight test Airtight test should be made by pressurizing nitrogen gas to 3Mpa. For the test method, refer to the following figure. (Make a test with the valve closed. Be also sure to pressurize both liquid and gas pipe.) The test result can be judged good if the pressure has not been reduced after leaving for about one day after completion of nitrogen pressurization. a. Nitrogen gas b. To indoor unit c. System analyzer d. Low knob e. High knob f. g. Valve Liquid gas h. Gas pipe i. j.
5. Drain piping •Incline the drain piping to the outside (drain side) as shown in the figure below. •The outlet of the indoor unit drain pipe is Rc1. •After completion of piping, confirm that drainage is good and that there are no leaks. Indoor unit drain piping Install thermal insulation to prevent dew The drain piping should have a drain trap. C Slope 20mm/m A Drain pan Drain piping B A> = 70mm B> = 2×C > = 70mm C> = 35mm Drain trap The drain pipe should extend below this level.
6. Electric wiring Construct the earth connection. All electrical work must be carried out by a suitable qualified electrical trades-person and in accordance with local supply authority requirements and associated regulators. The range of working voltage is within 10% voltage of power supply. The outdoor unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or HRC fuse.
Control module of outdoor unit PU-15 Control module of outdoor unit PU(H)-7, 8, 10 Upper blow In case of PU-7, 8, 10 In case of PUH-7, 8, 10 Terminal block for power supply wires F3 F3 52C & 51C F3 3.15A F3 3.15A 52C & 51C F3 2 52C1 & 51C1 T1 F3 3.
Method for connecting electric wire Please do the wiring after consulting the electric power company of jurisdiction beforehand in the instruction. (1) The entire wiring diagram of unit. a a b b PE PE j d c j In case of PE-7,8,10 In case of PE-15,20 PEH-5, 7, 8, 10 g a. Power supply b. Main switch/fuse (field supply) c. Power supply wiring for outdoor unit d. Power supply wiring for indoor unit e. Outdoor unit f. Indoor unit g.
(3) LCD remote controller. (3)-1. Confirmation of parts The following parts are contained in the carton box together with this manual. Please check to make sure that everything is included. Q'TY 1 Remote controller (upper case, lower case) ······································· 1 2 Pan-head screw with cross hole M4 ··················································· 2 3 Wooden screw 4.
(3)-4. Wiring (1) Connect the wires on the basis of the following wiring diagram. (2) Connecting work is different each models. (3) LCD remote controller cables must be installed away from the power cables so that they are not influenced by electrical noise from the power cables. (Do not place the LCD remote controller cables and power cables in the same conduit.) Caution : This controller is damaged if mistook the connection.
(3)-5. How to connect the external sensor (PAC-SE40TSA) to LCD remote controller. This controller is set for using internal sensor. If you need the external sensor, please consult your dealer and purchase option external sensor. (PAC-SE40TSA) And please change below method. Shunt jumper Shunt jumper 1. Remove the cover of LCD remote controller. 2. Connect the wire of external sensor to terminal as below. 3. Replace the shunt jumper from "INT" side to "EXT" side as below. Section A 4. Check above connection.
7. The putting condition of the belt (PE(H)-15,20 only) 1. Set the parallel angle of the fan and the motor pulley as shown in the table and figure 1 below. 2. Set the tension of the per one belt when the flexion load is within the range as shown in the figure 1 below at the proper flexion. (A=4.5mm) 3. Adjust the suitable tension after the belt sit properly across the pulley (after more 24-28 hours working). When the new belt is used, adjust the suitable tension about the 1.
INSTRUCTIONS FOR USE 1. Check points for operation Check the following points before you operate your air conditioner. (1)Check that there is nothing blocking the flow of air from the air outlet into the air inlet. Indoor unit Inlet grille Outlet grille Ceiling Ceiling Obstacle blocking air inlet Obstacle blocking air outlet Outdoor unit Obstacle blocking air inlet. (2)Make sure the air conditioner is properly grounded by checking the ground terminal.
2. Caution for use Keep the following points in mind to safeguard against failures and breakdowns. (1) This air conditioner does not restart within 3min. after shut down.(These models have a crankcase heater in the compressor. If the air conditioner is shut down for a short time, please do not turn the power switch to OFF, but turn the operation switch to OFF.) (2) If the air conditioner is shut down by a power failure, set the operation switch to OFF.
3.3 Cleaning the Outdoor Unit Heat Exchanger If you use your air conditioner for prolonged periods, the outdoor heat exchanger will become dirty, impairing its function and reducing air conditioners performance. Consult your equipment supplier or air conditioning contractor on how to clean the heat exchanger. Heat exchanger 4. The putting adjustment of the belt (PE(H)-15,20 only) The tension of the belt decrease with the passage of the drive time by total length's expands.
8. Transferring work, and construction 8.1 Transfer of installation 1. When removing and reinstalling the air conditioner when you enlarge your home, remodel, or move, consult with your dealer in advance to ascertain the cost of the professional engineering work required for transferring the installation. 2. Please do not mix the one other than a specified refrigerant when you add the refrigerant (R-22) at the installation and the transferring. 3.
9. Troubleshooting Before you ask for repair service, check the following points: State of Machine It does not run. Cause LCD remote controller “ON-OFF” display is not lit up. No display appears even when the [ON/ OFF] button is pressed. Troubleshooting Power failure. Press the [ON/OFF] button after power restoration. The power supply is turned OFF. Turn the power supply ON. The fuse in the power supply is gone. Replace fuse. The earth leakage breaker is gone. Put in the earth leakage breaker.
HOW TO OPERATE If you use the LCD remote controller, you can operate below method. Please consult operate method with dealer, if you use field supply control parts. Display section C 1. ON / OFF G B E H D F A J 1 E E Operation lamp Start an operation Press the [ON/OFF] button 1 Operation lamp lights up and operation starts. For purposes of explanation, all the displays on this page are shown in their lit condition. This configuration does not occur in the actual unit.
2. Selecting operation 3. Room temperature adjustment B D F 2 B 3 Operation mode display D When selecting operation Press the [MODE] button Set temperature display and F room temperature display To change room temperature 2 Consecutive press of the [MODE] button switches the operation over to “FAN”, “COOL”, “HEAT” and “AUTO”. For the contents of operation, check the display. For fan Press the [MODE] button 2 and bring up the “FAN” display.
4. Time setting 5. Other function A H J 5 1 8 9 5 10 4 A J 7 7 6 Current time display Timer Hold/Resume display 11 Key lock Press the [MINUTE] button 7 three times consecutively, the word “KEY LOCK” will displayed H . At this time, only [ON-OFF] button 1 is valid. This function purpose is protect from mischief of child etc. Clock setting Press the [CLOCK] key 4 one time will activate set clock mode. Press the [CLOCK] key 4 again will disable set clock mode.
LOW AMBIENT COOLING PARTS; OPTION PAC-205FC (Fan controller) 1. Outline This fan controller apply to following units. Model name Model name Q'TY PUH-5,8,10 (side blow) Q'TY PUH-15,20 PUH-7,8,10 (upper blow) 2 set 1 set PU-7,8,10 These units can be operated on cooling mode at the low ambient temperature with this optional FAN CONTROLLER. Please read carefully this manual and install following this. 2. Caution 1. Fan controller changes the outdoor fan speed.
4. Installation 4-1. PU(H)-7,8,10 Please use the following parts during installation of fan controller. There are two kinds of wiring sticker, please use writing as "ONLY PU(H)-7,8,10". Accessory assy 1 Wiring sticker Use Accessory assy 2 Spring Connector cap Screw Earth sticker Attachment Grommet Band Pipe cover Connector assy ONLY PU(H)-7,8,10 9 1 Accessory assy 1 Wiring sticker Screw 1 1 Accessory assy 2 Attachment Attachment 1 2 3 3 15 1 Not use 3 1 1 1 4-1-1. Install 4-1-2.
4-2. PUH-15,20 Please use the following parts during installation of fan controller. There are two kinds of wiring sticker, please use writing as "W881927". The fan controller is necessary for these models by two sets. (The following accessory parts show the fan controller one set.
4-3. PUH-5,8,10 (Side blow type) Please use the following parts during installation of fan controller. There are two kinds of wiring sticker, please use writing as "W881927". Accessory assy 1 Wiring sticker Spring Screw Accessory assy 2 Earth sticker Grommet Pipe cover Band Use 1 Wiring sticker Not use 3 1 Accessory assy 1 Screw Connector 1 2 3 Accessory assy 2 Attachment Attachment Attachment 15 Connector assy ONLY PU(H)-7,8,10 1 9 1 1 4-3-1. Install 1 4-3-2.
5. Before starting the trial run. Please execute the following confirmations to prevent wrong connection. If there is wrong connection, it may damage fan controller, but also damage the unit. Confirmation Please intercept the power supply without fail, and secure safety when you execute detaching wiring, the connector, and the measurement machine to the following work.
Cause Check point - 109 - 6) The fan motor and unit side control box are defective. Fan power supply wiring is connected with fan controller power supply taking out part, and confirm operation. Whether the voltage is input to fan motor is confirmed. Whether the fan motor operation is confirmed. When the voltage impression and fan motor does not work, fan motor is defective. When the voltage is not impressed to the fan, the unit side control box is defective.
- 110 - State of Machine Cause 3) Connected mistake 2) Output wiring supply reverse-phase. 1) Power supply reverse-phase. It becomes highpressure abnormal pressure. Something wrong occurs by step2-2 drive confirmation of installed confirmation matter. Check point The phase of U, V, W is corrected. Is the phase of U, V, W correct? Troubleshooting The phase of L1, L2,L3 is corrected. Content of confirmation Is the phase of L1, L2, L3 correct? The phase of U, V, W is corrected.
- 111 - 4. The fan never becomes full load drive. (In heating) State of Machine Item 1) is checked, again. 3) The control printing wiring board is defective. After checking item 1), there is a possibility of a defective printed circuit board if a normal drive is not done. The content of P14 is judgment. (SCRM) 2) The thyristor module (SCRM) is defective. The content of P14 is checked. (SCRM) The unit side connection is confirmed. CNU, CNV, CNW-SCRM (The connection is noted.
Thyristor module (SCRM) Measure the resistance between each of the SCRM pins and judge if there is a failure or not by the resulting values. Check between G and K. Use the smallest resistance range on the tester. Judgment Value: 1.5 ohm 80 ohm Check between AK1 and AK2. Use the greatest resistance range on the tester.
SPECIFICATION GUIDELINES Air to air reverse cycle split air conditioning system. The systems shall operate at out door ambient temperatures as high as __ ºC. The system shall have a total cooling capacity of __kW or greater with an indoor air quantity of __ L/s at __ ºC DB and __ ºC WB entering indoor coil temperature with a __ ºC temperature entering the outdoor coil. The system shall have a sensible heat capacity of kW or greater with a room DB temperature of __ ºC.