Specifications
-36-
SAFETY & CONTROL DEVICES
ACCESSORY AVAILABILITY
Compressor over current relay
High pressure switch
High pressure switch (defrost)
Indoor fan motor over current relay
Fuse (Control circuit)
Fuse (Operation circuit)
51C
51F1
51F3
F
F
PRHG-10MYA
2.16MPa OFF
6 ± 1.5 ˚C ON, 26 ± 1.5 ˚C OFF
2.94MPa OFF
22A 31.0A
2.8A 3.6A
63H
63H1-1, 1-2
63H2-1, 2-2
2.5A
2.94MPa OFF
6 ± 1.5 ˚C ON, 26 ± 1.5 ˚C OFF
3.15A
3.15A
ITEM
Outdoor fan motor over corrent relay
51F2 2.5A
Outdoor fan motor internal thermostat 49F 150 ˚C OFF
26D1, 2
Frost protector
26D
PRHG-15MYA PRHG-20MYA
PRHG-10MYA PRHG-15MYA PRHG-20MYA
PRHG-8MYA
PRHG-8MYA
PRHG-8MYA-EU
PRHG-10MYA-EU PRHG-15MYA-EU PRHG-20MYA-EU
(PRHG-8MYA-EUS) (PRHG-10MYA-EUS) (PRHG-15MYA-EUS) (PRHG-20MYA-EUS)
22A 31.0A
5.0A 7.5A
Low Ambient Cooling parts
Pressure Gauge
Fin guard
Anti corrosion
(Service ref.)
PAC-205FC
Special order
PAC-206PG
* Low Ambient cooling
It is possible to conduct cooling operation under an outdoor temperature even down to -5 ˚C.
Description
Model
Service ref.