Specifications
Mechanical Indicators
50
Specifications
Direct indicator
Note 1
Indicator
combined
with CT
Size (width ✕ height) mm
Model name
Operation principle
Accuracy (grade)
Frequency
Scale length (mm)
Weight (kg)
Indicator rating
64✕60
YR-206NAA
Delivery period classification
Page with outer dimensions drawing
55
0.1
70
0.1
85
0.15
70
0.1
90
0.15
100
0.3
2.5
124
0.3
1.5
175
0.5
200, 300mA
500mA
1, 3, 5mA
10, 20, 30, 50, 75mA
100, 200, 500mA
1, 3A
5, 10, 15, 20A
30A
/5A (indicator rating 5A)
/1A (indicator rating 1A)
Ordinary
—
1.4V
1.4V
1.2V
0.06VA
0.06VA
0.1VA
0.2VA
0.1VA
0.06VA
Expanded
—
—
—
—
0.3VA
0.3VA
0.3VA
—
0.3VA
0.3VA
Ordinary
1.7V
1.4V
1.4V
1.2V
0.06VA
0.06VA
0.1VA
0.2VA
0.1VA
0.06VA
Expanded
—
—
—
—
0.3VA
0.3VA
0.3VA
—
0.3VA
0.3VA
Ordinary
1.7V
1.4V
1.4V
1.2V
0.06VA
0.06VA
0.1VA
0.2VA
0.1VA
0.06VA
Expanded
—
—
—
—
0.3VA
0.3VA
0.3VA
—
0.3VA
0.3VA
Ordinary
1.7V
1.4V
1.4V
1.2V
0.06VA
0.06VA
0.1VA
0.2VA
0.1VA
0.06VA
Expanded
—
—
—
—
0.3VA
0.3VA
0.3VA
—
0.3VA
0.3VA
Ordinary
1.7V
1.4V
1.4V
1.2V
0.06VA
0.06VA
0.1VA
0.2VA
0.1VA
0.06VA
Expanded
—
—
—
—
0.3VA
0.3VA
0.3VA
—
0.3VA
0.3VA
Ordinary
1.7V
1.4V
1.4V
1.2V
0.06VA
0.06VA
0.1VA
0.2VA
0.1VA
0.06VA
Expanded
—
—
—
—
0.3VA
0.3VA
0.3VA
—
0.3VA
0.3VA
Ordinary
—
—
1.4V
1.2V
0.2VA
0.2VA
0.2VA
0.2VA
0.2VA
0.2VA
Expanded
—
—
—
—
0.2VA
0.2VA
0.2VA
0.2VA
0.2VA
0.2VA
Ordinary
—
—
1.4V
1.2V
0.2VA
0.2VA
0.2VA
0.2VA
0.2VA
0.2VA
Expanded
—
—
—
—
0.2VA
0.2VA
0.2VA
0.2VA
0.2VA
0.2VA
85✕75
YR-208NAA
100✕82
YR-210NAA
82✕82
YR-8NAA
102✕102
YR-10NAA
122✕122
YR-12NAA
80✕80
LR-80NAA
110✕110
LR-110NAA
Rectifier
2.5
Rectifier
2.5
50 and 60Hz
1.5
Rectifier
Maximum scale value
3735 36
Consumption VA or voltage drop
Standard
product
Immediate delivery
Quasi-standard
product
Within 20 days
Special
product
21 to 60 days
Symbol
Reference delivery period
Delivery period classification
Rectangular indicators Wide-angle indicators
L-N Series
Y-2N Series Y-N Series
YR-8NAAYR-206NAA
Uniform scale
Load
Fig. 1 AC ammeter (direct)
CT
Note 2
Load
Fig. 2 AC ammeter (combined with CT)
1
2
3
Load
CT
R
AA
T
Current
changeover
switch
Note 2
1
2
Fig. 3 AC ammeter (combination with 3-phase circuit
current changeover switch)
Connection diagrams
Indicator combined with current transformer
Model name
Model name
Indicator rating
Scale
CT ratio Cover type
Special specifications
Special specifications
Direct indicators
YS-8NAA
YS-8NAA
5A
Indicator rating
20A
0-100-300A
Scale
0-20-60A
Double scale, colored
lines, etc.
Double scale, colored
lines, etc.
BR
Cover type
GR
100/5A
The items in must be specified.
Number of
units
5
Number of
units
5
Remarks
Note 1.
(1) Error may occur due to waveform distortion.
(2) LR-110NAA and LR-80NAA models rated 100mA to 30A incorporate an approximate effective value
rectifying circuit.
(3) Please make sure to read the “Safety Precautions” (pp.5-8) and the “Selection Precautions” (p.9) to
assist in selecting the model and use specifications suited to the application.
The operating circuit voltage is 300V or less for the Y-2N Series, and 600V or less for the Y-N Series and L-N Series.
Note 2. For low-voltage circuits, grounding of the secondary side of the current transformer is unnecessary.
Ordering method