Specifications

178
Transducers
Peripheral transducers
±0.5%
±0.5%
0.5
T-101HAA(DS)
±0.25%
(both)
±0.25%
(both)
AC current demand
transducers
(moderate time interval)
AC voltage demand
transducers
(moderate time interval)
Current transducers with power
flow detection
±0.5%
±0.5%
0.5
T-101HAV(DS)
±0.25%
(both)
±1.0%
*3
±0.5%
±0.5%
0.5
±0.25%
T-101HAA(D)
±1.0%
±1.0%
1.0
T-51LG
T-51LGF
Leakage current
transducers
setting accuracy
±5%
T-101VDL
T-101VDH
Voltage drop detectors
Voltage rise detectors
For T-51LG, the % with respect to basal value that is the maximum value of the mutual difference between output values when the frequency is changed from
40 to 2kHz.
For T-51LGF, the % with respect to basal value that is the maximum value of the mutual difference between output values when the frequency is changed from
45 to 60Hz.
*2
120% of rated input value
Supply electricity for 10s duration 10 times at 10s intervals (temperature transducers excluded)
Supply electricity for 10s duration 10 times at 10s intervals (temperature transducers excluded)
2000VAC for 1min
2000VAC for 1min
2000VAC/DC for 1min (in combination with a ZCT for leakage current transducers)
2000VAC for 1min
10MΩ or more (at relative humidity of 80% or less)
±1500V, pulse width: 1ms
±1500V, pulse width: 1ms (leakage current transducers exempt)
490m/s
2
(50G), in 3 directions, 6 times with mounting legs mounted
16.7Hz, double amplitude 4mm, in 3 directions, 1h each (corresponding to approx. 2.2G) with mounting legs mounted
-10~50°C (daily mean temperature: 35°C or less)
-20~60°C
30~85% relative humidity