Specifications
170
Transducers
Number of units
5
Model name
T-120HA 4~20mA
Output
Voltage or current
Outer dimensions, and names and functions of respective parts
Terminal cover
M4 terminal screw
M3.5 terminal screw
Terminal cover
qOutput terminals
Mounting leg
IEC rail removal tab
IEC 35mm rail
For analog outputs of 10
elements.
wDisplay unit
Displays the setting screen.
Displays the analog output
pattern during operation.
eButtons
Used for setting and
checking values.
rInput terminals
For inputting the voltage,
current and auxiliary power
supply.
Connection diagrams
Analog outputs CH1~CH10
Auxiliary
power supply
Load
2
1
B
M
A
MNCANC
V
CT
CH1
CH2 CH3
CH4 CH5
CH6
CH7
CH8
CH9
CH10
NC
NC
CH1
CH2
CH3
CH4
CH5 CH6
CH7
CH8
CH9
CH10
NC
NC
k
K
L
For low-voltage circuits, grounding of the secondary sides of the instrument voltage transformer and current transformer is unnecessary.
Make sure to use after grounding the earth terminal ( ). Provide a D earth (earth resistance: 100Ω or less) for grounding. Inadequate grounding may
cause a malfunction.
As the lead wires for connecting the output and load of a transducer, use two-core shielded wires or twisted-pair wires to prevent malfunction and failure
due to transmission noise and disturbance surge. If the transmission distance exceeds 100m, current output specifications are recommended.
Do not bring the output line close to or bundle it together with other power lines or the input lines (VT, CT, and auxiliary power supply).
Ground the shield line of a shielded cable on the receiving side.
However, depending on the circumstances of external noise, it may be better to ground it on the transducer side.
NC is a connection-forbidden terminal.
NC
Fig. 1 With VT and CT
Analog outputs CH1~CH10
Auxiliary
power supply
Load
2
1
B
M
A
MNCANC
V
CT
CH1
CH2 CH3
CH4 CH5
CH6
CH7
CH8
CH9
CH10
NC
NC
CH1
CH2
CH3
CH4
CH5 CH6
CH7
CH8
CH9
CH10
NC
NC
k
K
L
NC
Fig. 2 With CT
u
v
U
V
VT
Ordering method