Specifications
168
Transducers
oFF (no limit): The upper-limit output is output to approx. +5% and the lower-limit output is output to approx. -5%.
on (with limit): The upper-limit output is output to approx. +1% and the lower-limit output is output to approx. -1%.
RETURN
SET
RETURN SET
SET
Analog output adjustment (zero adjust, span adjust)
Set in the range of -30~0~30
• During current output, adjustment by
approx. ±0.16mA can be performed.
• During voltage output, adjustment by
approx. ±0.05V can be performed.
Set in the range of -75~0~75
• During current output, adjustment by
approx. ±0.48mA can be performed.
• During voltage output, adjustment by
approx. ±0.15V can be performed.
RETURN SET
RETURN SET
RETURN SET
SET
20mA
4
Movement of zero adjustment value
Zero adjustment value
Input
Movement during span adjustment
Input
20mA
4
Span adjustment value
Unidirectional deflection
0
qSetting menu
qChange the setting menu to indicate .
buttons
qSetting menu
qChange the setting menu to indicate .
buttons
• This setting is not available with the 4-20mA specifications for analog output.
•
The same specifications are applied to all analog output CHs. Setting according to CH cannot be performed.
[Button functions]
or
: The set up mode is entered when this is pressed for 2s or more.
Used for selecting an item to be set, and setting various items.
: Used for increasing/decreasing a setting value during set up, and
for checking setting values.
: Used for selecting (setting back) an item to be set.
RETURN
SET
SET
RETURN
The underline in the setting specifications indicates
the default value at the time of factory shipment.
wSet the analog output to 1-5V or 0-5V.
buttons
w Analog output
0-5 or 1-5
wPerform zero adjustment of the analog output CH1.
buttons
w
Analog output CH1
zero adjustment
ePerform span adjustment of the analog output CH1.
buttons
e
Analog output CH1
span adjustment
r Perform zero adjustment and
span adjustment of analog output
CH2~CH10 in the same manner
1-5V (1-5V output) 0-5V(0-5V output)
eOutput limit
eSet the analog output when the full scale is exceeded.
buttons
When this is changed, the zero adjust and
span adjust are returned to the default
values at the time of factory shipment.
oFF (no limit) on (with limit)
r Continue setting in another setting menu or end setting.
(Refer to of “ Basic settings.”)
ySetting menu
buttons
rSetting menu
t Continue set up in another setting menu or end set up.
(Refer to of “ Basic settings.”)
ySetting menu
buttons
tSetting menu
ANALOG
ZERO SPAN
Analog output settings (Analog output 1-5V/0-5V, output limit)