Specifications

Setting Method
161
Transducers
qChange the setting menu to indicate .
(α: 1 for 1-phase, 2-wire system; 2 for 1-phase,
3-wire system; for 3-phase, 3-wire system)
However, calculate with the primary voltage being
100V for the 1-phase, 3-wire system.
For reactive power, the unit W is changed to var.
qChange the setting menu to indicate .
Pulse output settings (pulse output elements, pulse unit, pulse width)
PULSE
Analog output adjustment (zero adjust, span adjust)
Element that can be set
No.1 Wh
No.2 Wh
No.3 varh
No.4 varh
No.5 varh
No.6 varh
No.7 varh
No.8 varh
None
0.125s
0.500s 1.000s
1k 0.1k 0.01k 0.001k
10k 1k 0.1k 0.01k
100k 10 k 1k 0.1k
1000k 100 k 10k 1k
10M 1M 0.1M 0.01M
100M 10M 1M 0.1M
Full-load active power (kW)=
α (primary voltage) (primary current)
1000
ZERO SPAN
qSetting menu
tPulse width
ySetting menu
qSetting menu
tSetting menu
w Pulse output
CH11 element
e Pulse output
CH1 pulse unit
w
Analog output CH1
zero adjustment
r
Set the element and
pulse unit for pulse
output CH2 in the
same manner.
wSet the element (No.) to be output to the pulse output CH11 (C1A-C1B).
Select from the table below in accordance with the full-load active power.
eSet the pulse unit for the pulse output CH11 (C1A-C1B).
rThe same elements as those of CH11 can be set for the pulse output CH2 (C2A-C2B).
tSet the pulse width
yContinue set up in another setting menu or end set up.
w Perform zero adjustment of the analog output CH1.
Set in the range of -30~0~30
• During current output, adjustment of approx.
±0.16mA can be performed.
• During voltage output, adjustment of approx.
±0.05V can be performed.
Element (indication) Pulse output element (measurement range)
Active electric energy (receiving) (pulse output CH11)
Active electric energy (sending)
Reactive electric energy (receiving, lag) (pulse output CH12)
Reactive electric energy (receiving, lead)
Reactive electric energy (sending, lag)
Reactive electric energy (sending, lead)
Reactive electric energy (receiving, lag + sending, lead)
Reactive electric energy (receiving, lead + sending, lag)
No pulse output element
Full-load active power (kW)
Less than 10
10 or more and less than 100
100 or more and less than 1000
1000 or more and less than 10000
10000 or more and less than 100000
100000 or more
Pulse unit (Wh/pulse) that can be set
The same specifications are applied to all pulse output CHs. Setting according to CH
cannot be performed.
If the load is large when the pulse width is set to 0.500s or 1.000s and the pulse unit is set
to the minimum value, the number of pulse outputs may decrease because the pulse
output cannot follow. Use the following relationships to calculate the setting for which the
OFF time of the pulse output will not be shorter than the ON time for all loads.
When 0.500s is set: full-load active power/pulse unit3600
When 1.000s is set: full-load active power/pulse unit1800
tContinue set up in another setting menu or end set up.
(Refer to of “ Basic settings.”)
iSetting menu
e
Analog output CH1
span adjustment
r
Perform zero adjustment and
span adjustment of analog output
CH2~CH10 in the same manner
e Perform span adjustment of the analog output CH1.
Set in the range of -75~0~75.
• During current output, adjustment of
approx. ±0.48mA can be performed.
• During voltage output, adjustment of
approx. ±0.15V can be performed.
(Refer to of “ Basic settings.”)
iSetting menu
20mA
4
Zero adjustment value
Input
Input
Input
20mA
4
Movement during span adjustment
Movement of zero adjustment value
Span
adjustment
value
Unidirectional deflection
0
Span
adjustment
value
Bidirectional deflection
0
RETURN
SET
RETURN
SET
RETURN
SET
RETURN
SET
SET
RETURN
SET
RETURN
SET
RETURN
SET
SET
buttons
buttons
buttons
buttons
buttons
buttons
buttons
buttons
buttons