Specifications
Setting Method
159
Transducers
Setting method
i Continue set up in another
setting menu or end set up.
To change to another setting menu,
use the and buttons to
select the setting menu in which
set up is to be performed.
To end set up
Use the and buttons to select End.
Use the button to display SAVE, and
then save the settings by pressing the
button again.
To cancel the settings
When SAVE is displayed, use the and
buttons to select CANL and then press
the button to cancel the settings.
[Display unit]
Setting mode
Press the button for 2s or more to enter the set up mode (setting menu will be displayed and “End” will blink).
Use the and buttons to select the item to be set, press the button to display the set up screen,
and then use the and buttons to set the contents.
When the button is pressed for 1s or more while setting an item, setting of the remaining items is
skipped and returns to the setting menu.
Basic settings (analog output pattern, phase-wire system, frequency, primary/secondary voltages, primary current)
qSetting menu
w
Phase-wire system
rFrequency
t
Secondary voltage
y
Primary voltage
u
Primary current
eAnalog output
pattern
qChange the setting menu to indicate .
w
Set the phase-wire system. (When this setting is changed, all other settings are set back to the default settings at the time of factory shipment.)
rSet the frequency.
50Hz
t
Set the secondary voltage.
110V
If the 1-phase 3-wire system is set in w,
the input rating will differ according to the
secondary voltage setting.
y
Set the primary voltage. (When this is changed, the measurement ranges for active power and reactive
power are set back to the default settings at the time of factory
shipment.)
u
Set the primary current. (When this is changed, the measurement ranges for active power and reactive
power are set back to the default settings at the
time of factory shipment.)
110V
220V
440V
1100V
2200V
3300V
6600V
11kV
13.2kV
16.5kV
22kV
33kV
66kV
77kV
110kV
132kV
154kV
187kV
220kV
275kV
550kV
SP
• If the 1-phase 3-wire system is set in w, setting of the primary
voltage will be skipped.
• If the secondary voltage is set to 220V in t, setting of the
primary voltage will be skipped.
•
When SP is selected, setting of the special primary voltage is entered,
in which the upper three digits can be set in the range of 110V to 550kV.
5A
6A
7.5A
8A
10A
12A
15A
20A
25A
30A
40A
50A
60A
75A
80A
100A
120A
150A
200A
250A
300A
400A
500A
600A
750A
800A
1000A
1200A
1500A
1600A
2000A
2500A
3000A
4000A
5000A
6000A
7500A
8000A
10kA
12kA
20kA
25kA
30kA
SP
•
When SP is selected, setting of the special primary current is entered, in
which the current can be set in the range of 5A to 30kA in the following steps.
5A~100A : in steps of 5A
100A~1000A : in steps of 10A
1000A~10kA : in steps of 100A
10kA~30A : in steps of 1kA
Analog output setting indicator
Basic setting indicator
Operation indicator
Lit during operation.
Output channel display
Displays the output channel to be set.
Pulse output element display
Displays the pulse output element to be set.
Demand time interval setting indicator
Lit when setting the demand time interval
for active power, current and harmonics.
Harmonics measurement setting indicator
Lit when setting harmonics measurement.
Harmonics measurement pattern display
Displays the measurement pattern to be set.
%: content (%) RMS: effective value
Output limit setting indicator
Lit when setting the output limit.
Zero adjust indicator
Pulse output setting indicator
Span adjust indicator
Test indicator
Lit during analog output testing.
Digital display, unit indicator
The respective setting values are displayed.
Setting indicators are lit when setting
the corresponding item.
Measurement elements
Phase-wire system
Analog output
pattern
CH1
P01 V
12
V
23
V
31
I
1
I
2
I
3
W PF var Hz
P02 V
12
HV
12
V
31
I
1
I
2
HI
1
W PF var Hz
3-phase 3-wire system
1-phase 3-wire system
P03 V
12
V
23
V
31
I
1
I
2
I
3
WPFHV
12
HI
1
1-phase 2-wire system
P01 V
12
HV
12
—I
1
—HI
1
W PF var Hz
The pattern is fixed at P01 in the case of the 1-phase 2-wire system
HI: harmonic current, HV: harmonic voltage,
-: no measurement element (fixed at lower limit output)
eSet the analog output pattern.
P01
Input ratingSecondary
voltage setting
V
12
V
23
V
31
110V 0~150V
220V 0~300V
0~300V
When this is changed, the
measurement ranges for
active power and reactive
power are set back to the
default settings at the time
of factory shipment.
3P3 (3-phase 3-wire system) 1P2 (1-phase 2-wire system)1P3 (1-phase 3-wire system)
P02 P03
60Hz
220V
CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10
RETURN
SET
buttons
buttons
buttons
buttons
buttons
buttons
buttons
buttons
SET
SET
SET
SET
RETURN
SET
RETURN
SET
RETURN
SET
RETURN
SET
RETURN
SET
SET
SET
SET
SET
i
Setting menu