Specifications

T-120M collective Multi-transducers
157
Transducers
With multi-transducers, the required AC electric quantities can be measured by inputting the secondary sides of a VT and CT.
Measurement elements
• Analog outputs
AC voltage, AC current, active power, reactive power
Power factor, Frequency
Harmonic voltage, harmonic current
• Pulse outputs
Active electric energy, reactive electric energy
Block diagram
Voltage
Current
Active power
Reactive power
Power factor
Frequency
Harmonic voltage
Harmonic current
Active electric energy (pulse)
Reactive electric energy (pulse)
(Receiver)
Indicator
Recorder
Control equipment
Data logger
Calculator
Sequencer
Telemeter
Input
T-120M multi-transducer
VT
CT
Phase-wire
system
3-phase
3-wire system
1-phase
3-wire system
1-phase 2-wire system
Analog output
pattern
P01
P02
P03
P01
V
12
V12
V12
V12
CH1
V
23
HV12
V23
HV12
CH2
V
31
V31
V31
CH3
I
1
I1
I1
I1
CH4
I
2
I2
I2
CH5
I
3
HI1
I3
HI1
CH6
W
W
W
W
CH7
PF
PF
PF
PF
CH8
var
var
HV
12
var
CH9
Hz
Hz
HI
1
Hz
CH10
Wh, Varh
(set using switch)
Pulse outputAnalog output
Measurement element
CH11 CH12
The output pattern is fixed at P01 for 1-phase, 2-wire systems.
HI: Harmonic current, HV: Harmonic voltage, -: No measurement element (fixed at lower limit output)
Various elements can be measured with one unit.
A liquid-crystal display and buttons enable setting flexibility.
Supports power flow measurement (sending, receiving) and can be used for monitoring power generating equipment.
(Active power, reactive power, power factor, active electric energy, reactive electric energy)
Compact size realizes reducted mounting space.
Features
Analog output patterns