Specifications
Transducers
154
Signal line connection distance
The connection distance depends on conditions such as the output signal line specifications of the transducer, signal line
installation method, external magnetic field and electric field, and cannot be determined unconditionally. However, empirically
speaking, the lengths shown below should be used as a reference.
Applicable crimp terminals and tightening torques
Voltage signal output
Current signal output
Transducer output Connection distanceConnection conditions
10mm or less
300m or less
2km or less
Series Tightening torque
0.98~1.47N•m
T-51, T-101 Round crimp terminals (outer diameter: f8.5 or less) for M4 screws
Applicable crimp terminals
Outer diameter dimension
Transducer
0.5mm
2
~2mm
2
f0.65 or more
IV, KV, CVV
Data logger,
central monitoring
panel
VT
A
CT
Transducer
0.5mm
2
~2mm
2
f0.65 or more
CVVS, CPEVS, SPEVS
E
D
Data logger,
central monitoring
panel
VT
B
CT
If the signal line runs in
parallel to a power line,
secure the separation
distance in the table on
the right.
Condition
Low-voltage power lines of 600V or less
Other high-voltage power lines
Distance
30cm or more
60cm or more
Transducer
0.5mm
2
~2mm
2
f0.65 or more
CVVS, CPEVS, SPEVS
Line resistance: 200Ω or less
E
D
Data logger,
central monitoring
panel
VT
C
CT
If the signal line runs in parallel to a power line, secure the separation
distance shown in the table above. If this is not possible, provide
electromagnetic shielding by using a shield plate or conduit.